[PI Max Error]

This parameter is used with the process PI loop and sets
the PI error value which activates CR1-4 (if selected).The
relay(s) will be activated when [PI Error] exceeds this
value.

Parameter Number

293

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq Forward

Factory Default

Maximum Freq Forward

Minimum Value

–400.00 Hz

Maximum Value

400.00 Hz

[Pulse Out Select]

– Stand-Alone Version Only

This parameter selects the source value that drives pulse
output.

Parameter Number

280

Parameter Type

Read and Write

Factory Default

“Output Freq”

Units

Display Drive Range

“Output Freq” 0

See [Output Freq]

“Encoder Freq” 1

See [Encoder Freq]

“Acc/Dec Freq” 2

See Note

Note: Output frequency command of the drive directly at the output of the accel/decel ramp gen-
erator. It does not include any modification due to selected speed regulation mode via [Speed
Control].

[Pulse Out Scale]

– Stand-Alone Version Only

Provides a scaling factor for pulse output.

Pulse Output Rate = Hz x [Pulse Out Scale]

The pulse output will not provide a rate lower than 21 Hz.
A command less than 21 Hz will generate 0 Hz output. To
provide smooth operation across a wide speed range,
select the maximum scale factor possible.

Parameter Number

281

Parameter Type

Read and Write

Display Units / Drive Units

Factor / Factor

Factory Default

1

Minimum Value

1

Maximum Value

64

Example:
[Pulse Out Select] is set to “Output Freq” and drive is programmed for [Maximum Freq] = 60 Hz.
When the drive output is 60 Hz, the Pulse Output Rate is adjustable from 60 Hz (60 x 1) to 3840
Hz (60 x 64).

[Pulse In Scale]

– Stand-Alone Version Only

Provides a scaling factor for the pulse input.

Parameter Number

264

Parameter Type

Read and Write

Display Units / Drive Units

Factor / Pulses per Rev

Factory Default

64 PPR

Minimum Value

1

Maximum Value

4096

Example:
4 Pole Motor, 60 Hz = Max. Speed.
The 1336-MOD-N1 option outputs 64 Hz/Hz. At full analog reference, the pulse input to the drive
will be 60 Hz x 64 Hz/Hz = 3840 pulses/sec.

[At Time]

Sets the delay time for the activation of the CR1-4 relays.
The relay is activated at Start + [At Time] seconds. This
delay affects all relays.

Parameter Number

327

Parameter Type

Read and Write

Display Units / Units

0.01 Second / Seconds x 100

Factory Default

0.00 Sec

Minimum Value

0.00 Sec

Maximum Value

360.00 Sec

[Remote CR Output]

Individual bits control relay outputs when selected with
[CR1-4 Out Select]. 1 = Energize Coil. This parameter is
reset to the default on power-up.

Example:
If [CR2 Out Select] is set to “Remote,” bit 1 of this parameter
will control CR2.

A Status description (bit ENUM) is displayed on line 1
(except Series A HIMs below version 3.0).

Parameter Number

326

Parameter Type

Read and Write

Factory Default

xxxx0000

Scale

Factor

Incoming Pulse Rate (Hz)

Desired Command Freq.

=

Scale Factor =

3840 Hz

60 Hz

= 64

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

CR1 Output
CR2 Output
CR3 Output
CR4 Output
Not Used