Encoder Feedback

[Encoder Counts]

Displays the scaled encoder count value. The value is
incremented in the forward direction and decremented in
the reverse direction. Requires a quadrature (dual
channel) encoder and a value in [Enc Count Scale].

Parameter Number

283

Parameter Type

Read and Write

Display Units / Drive Units

1 Count / Counts

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

[Enc Count Scale]

Sets the scale factor for the incoming encoder pulse count.

Parameter Number

282

Parameter Type

Read Only

Display Units / Drive Units
Factory Default

1000

Minimum Value

1

Maximum Value

4096

[Encoder Loss Sel]

Selects the drive action when a missing or incorrect
encoder signal is detected.

Parameter Number

284

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disable” 0

After 200ms of encoder loss, a
warning will be issued.

“Enable” 1

After 200ms of encoder loss, an
alarm and an F60 fault will be
issued.

[Encoder Freq]

Not available.

Parameter Number

63

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

+400.00 Hz

[Max Enc Counts]

Sets the trip point for the “Enc Cnt Max” alarm. The alarm
is high (1) when [Encoder Counts] has exceeded [Max Enc
Counts].

Parameter Number

328

Parameter Type

Read and Write

Display Units / Drive Units

1 Count /Counts

Factory Default

0

Minimum Value

0

Maximum Value

32767

ATTENTION: To guard against possible machine damage and/or personal
injury, be aware that the maximum encoder count value in either direction is

±

32767. If the scale factor or number of pulses exceed this value, the [Encoder

Counts] parameter will roll-over from maximum positive to maximum negative
(or maximum negative to maximum positive). This roll-over must be considered
in applications that use this value.

!

[Encoder Counts] =

Number of Incoming Pulses

[Enc Count Scale]