Pi status, Pi ref select, Process pi – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual

Page 125

Advertising
background image

Programming

7–53

Process PI

[PI Status]

This parameter displays the status of the Process PI
regulator.

Parameter Number

214

Parameter Type

Read Only

Factory Default

None

[PI Ref Select]

The source of the PI reference is selected with this
parameter. The value from the selected reference is the
“set point” for the Process PI regulator.

The drive is capable of responding to a loss of the 4-20
mA signal used as either a PI reference or PI feedback.
Response to loss of 4-20 mA signal is controlled by
programming and requires the following:

a) [Speed Control] must be set to “Process PI”

and

b) Either [PI Ref Select] or [PI Fdbk Select] must be set to

“4-20 mA.”

If both of the above conditions are met, the signal loss
response is controlled by the setting of [4-20 mA Loss Sel].
If this parameter is set to “Stop/Fault,” loss of input will
cause the drive to stop and issue a Hertz Err Fault. Loss
of input while any other setting of [4-20 mA Loss Sel] is
chosen will cause the drive to activate the alarm bit (bit 6
of [Drive Status] and bit 13 of [Drive Alarm]) and output
programmed [Minimum Freq].

Signal loss protection is offered for the 2-10V input.

Parameter Number

215

Parameter Type

Read/Write

Factory Default

“Preset 1”

Units

Display Drive

“Use Last” 0

“Analog In 0” 1
“Analog In 1” 2
“Analog In 2” 3

“Pulse Ref” 4

Refer to [Pulse In Scale] Value

“MOP” 5

“Adapter 1-6” 6-11

“Preset 1-7” 12-18

“Encoder” 19 Refer to [Encoder PPR] Value

Diagram 1

Time

Enable

PI

Output

Command

Output

Freq.

Disable

0

24

21

27

30

18

15

12

9

6

3

Enable PI output integrates from zero – drive ramps

to regulated frequency.

Disable PI output is forced to zero – drive ramps to

unregulated frequency.

Enable PI output steps to preload and integrates

from there – drive steps to preload and
ramps from there.

Disable PI output is forced to zero - drive ramps to

unregulated frequency.

Enable PI output integrates from preload – drive

ramps from preload.

Disable PI output is held at preload - drive ramps to

unregulated speed (min. preload).

Note:

Drive will step output equal to preload on

Diagram 2

Enable

Disable

0

24

21

27

30

18

15

Preload

12

9

6

3

Diagram 3

Enable

Disable

0

24

21

27

30

18

15

12

9

6

3

Preload

Preload

Preload at Start

Preload at Start

Preload

Feed forward effect for
more dynamic

Better response for
well defined

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

Enabled
Spares