CE Conformity

Requirements for Conforming
Installation

The following items are required for CE conformance:

1. Standard 1336

SPIDER

CE compatible drive with integral filter.

2. Grounding and cabinet layout as shown in Figures C.1 and C.2.

3. Output power (drive to motor) wiring must be braided. For

shielded cable it is recommended to use a compact strain relief
connector with double saddle clamp for filter and compact strain
relief connector with EMI protection for motor output. Typical
shielded cable is shown below.

4. Control (I/O) and signal wiring must be in conduit or have

shielding with equivalent attenuation.

RFI Filter Leakage Current

The RFI filter may cause ground leakage currents. Therefore a solid
ground connection must be provided as shown below.

Electrical Configuration

Figure C.1
Grounding

!

ATTENTION: To guard against possible equipment
damage, RFI filters can only be used with AC supplies that
are nominally balanced and grounded with respect to
ground. In some installations, three-phase supplies are
occasionally connected in a 3-wire configuration with one
phase grounded (Grounded Delta). The filter must not be
used in Grounded Delta supplies.

Stranded Copper Wire

Plastic Insulation

Inner Plastic Sheath

Compact Screen of Galvanized (Tinned)
Copper or Steel braid

Outer Plastic Jacket

L1 (R)

L2 (S)

L3 (T)

PE

Conduit/4-Wire Cable

Nearest
Building Structure Steel

PWR
RUN
STOP
FAULT

TB1

TB2

TB3

TB4

TB5

TB6

TB7

DEVICE IS LIVE UP TO
180SEC AFTER REMOVING
MAINS VOLTAGE.
GERÄT FÜHRT BIS
180SEK NACH DEM
AUSSCHALTEN SPANNUNG.
L'APPAREIL RESTE SOUS
TENSION JUSQU'A 180 S
APRES LA MISE HORS SERVICE.