Programming

Feature Select

[Slip Comp Gain]

This parameter is the gain for the slip compensation and
adjusts the recovery rate after a load change.

Parameter Number

195

Parameter Type

Read and Write

Display Units / Drive Units

None

Factory Default

1

Minimum Value

1

Maximum Value

40

[Run On Power Up]

This parameter enables the function that allows the drive
to automatically restart on Power Up. This parameter
requires that a two wire control scheme be installed at TB4-
TB6 and that a valid start contact be present. Refer to Input
Mode Selection
in Chapter 3 or 4.

Parameter Number

14

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[Reset/Run Tries]

This value sets the maximum number of times the drive
attempts to reset a fault and restart before the drive issues
a “Max Retries Fault”. See Chapter 8 for a list of resettable
faults.

Parameter Number

85

Parameter Type

Read and Write

Display Units / Drive Units

1 Try / Tries

Factory Default

0

Minimum Value

0

Maximum Value

9

[Reset/Run Time]

This value sets the time between restart attempts when
[Reset/Run Tries] is set to a value other than zero.

Parameter Number

15

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Second / Seconds x 100

Factory Default

1.0 Sec

Minimum Value

0.5 Sec

Maximum Value

30.0 Sec

[S Curve Enable]

This parameter enables the fixed shape S curve accel/
decel ramp. Programmed accel/decel times are doubled if
[S Curve Time] is set to “0”. An adjustable S curve will be
created if [S Curve Time] is greater than zero.

Parameter Number

57

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[S Curve Time]

This creates an adjustable s curve ramp. If S Curve Time
is < the programmed accel/decel time, the actual ramp will
be the sum of the two. If S Curve Time is

the programmed

accel/decel times, a fixed S curve will be created whose time
is double the programmed accel/decel time.

Parameter Number

56

Parameter Type

Read and Write

Display Units / Drive Units

0.1 Second / Seconds x 10

Factory Default

0.0 Sec

Minimum Value

0.0 Sec

Maximum Value

1800.0 Sec

ATTENTION: This parameter may only be used as outlined in NFPA79, “Under
Voltage Protection.” Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application.

!