Derating guidelines, Power dissipation, Altitude – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual

Page 149

Advertising
background image

Specifications and Supplemental Information

A–3

Power Dissipation

Derating Guidelines

Drive ratings can be affected by a number of factors. If more than one
factor exists, derating percentages must be multiplied.

Shading indicates Drive [Rated Amps], “ * ” Indicates No Overload.

1

For 20 seconds every 10 minutes. The maximum [Current Limit] setting is shown.

2

The maximum [Current Limit] setting is shown. Normal Duty (ND) = 100%, 110% for 1 minute to 10
minutes, peak current for 3 seconds.

3

Note that parameter 13, [DC Hold Level] must NOT be set to 150%, but maximum as follows:
(A022) 140%, (A036) 140%, (A060) 100%, (B010) 70%, (B017) 70%, (B033) 70%.

4

The dynamic braking current is only defined by the external resistor. There is no internal current control
nor short circuit protection. Respective measures as bimetal relay, klixon etc have to be taken externally.

5

See Chapter 2 for dynamic brake resistor wiring information and Appendix B for dimension information.

Voltage

Catalog
Number

Peak
Current

Carrier Frequency, 50 Degree C Ambient
2 kHz

4 kHz

8 kHz

Cont.
Current

Power Dissipation Formula
I

L

= RMS Load Current

Cont.
Current

Power Dissipation Formula
I

L

= RMS Load Current

Cont.
Current

Power Dissipation Formula
I

L

= RMS Load Current

200-240V

1336Z-xA022

21.6A

9.0A

P=29W+(I

L

x 4.4V)+(I

2L

x 0.17)

9.0A

P=29W+(I

L

x 4.9V)+(I

2L

x 0.17)

9.0A

P=29W+(I

L

x 5.4V)+(I

2L

x 0.17)

1336Z-xA036

36.0A

15.0A

P=33W+(I

L

x 4.4V)+(I

2L

x 0.10)

14.0A

P=33W+(I

L

x 4.9V)+(I

2L

x 0.10)

10.0A

P=33W+(I

L

x 5.4V)+(I

2L

x 0.10)

1336Z-xA060

60.0A

30.0A

P=40W+(I

L

x 4.4V)+(I

2L

x 0.05)

25.0A

P=40W+(I

L

x 4.9V)+(I

2L

x 0.05)

18.0A

P=40W+(I

L

x 5.4V)+(I

2L

x 0.05)

380-480V

1336Z-xB010

9.9A

8.5A

P=29W+(I

L

x 5.5V)+(I

2L

x 0.36)

5.5A

P=29W+(I

L

x 7.8V)+(I

2L

x 0.36)

1336Z-xB017

16.0A

10.0A

P=33W+(I

L

x 5.5V)+(I

2L

x 0.22)

6.0A

P=33W+(I

L

x 7.8V)+(I

2L

x 0.22)

1336Z-xB033

33.0A

17.0A

P=40W+(I

L

x 5.5V)+(I

2L

x 0.11)

10.0A

P=40W+(I

L

x 7.8V)+(I

2L

x 0.11)

Voltage
Rating

Drive
Catalog
No.

Carrier
Frequency

Synch./Synch. Reluctance Motors

Induction Motors

DC Brake
Current

3

Dynamic Brake
Current

4,5

F.L.A.

Current Limit

1

F.L.A.

Current Limit

2

kHz

Ta=50˚C Ta=45˚C Ta=40˚C Peak Current

Ta=50˚C Ta=45˚C Ta=40˚C Peak Current at 0 Hz

A

rms

A

DC

/R

min

200-240V

A022

2

9A

9A

9A

21.6A = 240%

9A

9A

9A

14.4A = 160% 160%

12.6

15A/25 Ohms

4

9A

9A

9A

9A

9A

9A

8

9A

9A

9A

9A

9A

9A

A036

2

15A

15A

15A

36A = 240%

13.9A

15A

15A

24A = 160%

118%

21.0

15A/25 Ohms

4

14A

15A

15A

13A

15A

15A

8

10A

12.5A

15A

11A

13.6A

15A

A060

2

30A

30A

30A

60A = 200%

24A

28.2A

30A

48A = 160%

101%

30.0

23A/16 Ohms

4

25A

30A

30A

23A

26.5A

30A

8

18A

22A

26A

18A

23.8A

27A

380-480V

B010

2

8.5A

9.9A

9.9A

9.9A = 100%

8.5A

9.9A*

9.9A*

9.9A = 100%

89%

7.0

10A/75 Ohms

4

5.5A

6.4A

7.3A

5.5A

8.4A

9.9A*

B017

2

10.0A

11.5A

13.0A

16.5A = 127%

9.5A

11.6A

13A

16.5A = 127% 105%

9.1

14A/53 Ohms

4

6.0A

7.2A

8.4A

6.0A

9.6A

11.1A

B033

2

17A

20A

23A

33A = 143%

16.8A

19.9A

23A

33A = 143%

101%

16.1

17A/43 Ohms

4

10A

12A

14A

14A

16.5A

19A

Altitude

% of Drive

Rated Amps

Altitude

m

(ft)

100%

80%

90%

0

4,000

(13,200)

3,000

(9,900)

2,000

(6,600)

1,000

(3,300)

Altitude – All Drive Ratings