Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual

Page 71

Advertising
background image

Start-Up

6–13

Set Electronic

Overload

21. Electronic overload protection is factory set to drive maximum.

A. To properly set the electronic overload protection, program [Overload Amps]

(Setup group) to the actual nameplate F.L.A.

B. If the motor speed range is greater than 2:1, program [Overload Mode] to

the proper derate.

For the typical steps involved when programming, refer to step 15.

22. This completes the basic start-up procedure. Depending on your application,

further parameter programming may be required. Refer to Chapter 7 for
information.

23. If password protection is enabled, log out as described in Chapter 5.

Advanced Start-Up Procedure

Press these keys . . .

while following these steps . . .

The HIM Display will show . . .

Advertising