The following parameter appears only in the Linear List and is not
documented elsewhere.
Linear
List
This group lists all the parameters currently installed in your drive in numerical order. Refer
to the Appendix at the back of this manual for an alpha/numeric listing of all parameters.
[Bidir In Offset]
Trims the offset of the bi-directional inputs on LA6 & LA7
option cards. To provide an equal response to positive and
negative signals, this parameter may need to be adjusted
for each board. With no voltage on input 0, monitor [Anlg
In 0 Freq] and adjust [Bidir In Offset] until it is zero.
Parameter Number
329
Parameter Type
Read and Write
Display Units / Drive Units
None
Factory Default
270
Minimum Value
0
Maximum Value
1024