8–10

Troubleshooting

Table 8.E

(continued)

Alarm Conditions

Alarm

Bit

Alarm Name

Description

[Drive
Alarm 2]

0

Motor Therm

The value at the thermistor terminals has been exceeded. This bit will be active only when [Motor
Therm Flt] is enabled and an analog option board with thermistor input is installed.

1

Load Loss

[Load Loss Detect] is set to “Enabled” and the drive output torque current was below [Load Loss
Level] for a time period greater than [Load Loss time].

2

Encoder Loss

Error has occurred in the encoder signals.

3

Enc Cnt Set

[Encoder Counts] has reached the endpoint of

±

32767

.

4

Enc Cnt Max

The value of [Encoder Counts] has exceeded [Max Enc Counts].

5

Voltage Check

Voltage at drive output terminals is equal to, or greater than 10% of drive rated volts (i.e. 46V for 460V
drive) when Start command is issued and flying start is disabled. Drive will not start until terminal
voltage falls below 10% of drive rating or flying start is enabled.