Encoder freq, Pulse freq, Mop freq – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual

Page 78: Heatsink temp, Power ol count, Motor ol count, Last fault

Advertising
background image

7–6

Programming

Metering

[Encoder Freq]

Not available.

Parameter Number

63

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

+400.00 Hz

[Pulse Freq]

– Stand-Alone Version Only

This parameter displays the frequency command present
at the pulse input terminals. This value is displayed
whether or not this is the active frequency command.

Parameter Number

254

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

–400.00 Hz

Maximum Value

+400.00 Hz

[MOP Freq]

– Stand-Alone Version Only

This parameter displays the frequency command from the
MOP. The MOP frequency command can be adjusted by
TB5 & TB6 (if present) and appropriate inputs are selected
(see page

3–5

or

4–5

). Some SCANport adapters,

including the RIO Adapter, can also adjust the MOP
frequency command. This value is displayed whether or
not this is the active frequency command.

Parameter Number

137

Parameter Type

Read Only

Display Units / Drive Units

0.01 Hertz / 32767 = Maximum Freq

Factory Default

None

Minimum Value

0.00 Hz

Maximum Value

400.00 Hz

[Heatsink Temp]

This parameter displays the heatsink temperature of the
drive.

Parameter Number

70

Parameter Type

Read Only

Display Units / Drive Units

1

°

C / Deg. C

Factory Default

None

Minimum Value

0

Maximum Value

255

°

C

[Power OL Count]

Displays the percentage of accumulated I

2

t for the drive

thermal overload protection. Running continuously above
131% of drive rated amps will accumulate a value of 100% and
generate a Power Overload Fault (F64).

Parameter Number

84

Parameter Type

Read Only

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

None

Minimum Value

0%

Maximum Value

200%

[Motor OL Count]

This parameter displays the percentage of accumulated
I

2

t for the motor overload protection. Running continuously at

programmed [Overload Amps] will accumulate approximately
70%. Reduction of load will reduce the OL count. 100% value
will generate an Overload Fault (F07).

Parameter Number

202

Parameter Type

Read Only

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

None

Minimum Value

0%

Maximum Value

200%

[Last Fault]

This parameter displays the last drive fault. It is updated
whenever a new fault occurs.

Parameter Number

4

Parameter Type

Read Only

Display Units / Drive Units

Fault Number / Fault Number

Factory Default

None

Minimum Value

None

Maximum Value

None

Frequency

Displayed

Incoming Pulse Rate (Hz)

[Pulse Scale]

=