Feature Select

[Traverse Dec]

Sets the time period of decreasing frequency. Setting this
parameter to zero disables the traverse function.

Parameter Number

304

Parameter Type

Read and Write

Display Units / Drive Units

0.01 Second / Seconds x 100

Factory Default

0.00 Sec

Minimum Value

0.00 Sec

Maximum Value

30.00 Sec

[Max Traverse]

This value sets the peak amplitude of speed modulation.

Parameter Number

79

Parameter Type

Read and Write

Display Units / Drive Units

0.01 Hertz / 32767 = [Maximum Freq]

Factory Default

0.00 Hz

Minimum Value

0.00 Hz

Maximum Value

50% of [Maximum Freq]

[P Jump]

This value sets the slip or inertia compensation amplitude
of speed modulation.

Parameter Number

80

Parameter Type

Read and Write

Display Units / Drive Units

0.01 Hertz / 32767 = [Maximum Freq]

Factory Default

0.00 Hz

Minimum Value

0.00 Hz

Maximum Value

25% of [Maximum Freq]

[Bus Regulation]

Enabling this parameter causes the drive to adjust output
frequency based on the DC bus voltage. If the drive senses
rising bus voltage, it will increase the output frequency to
reduce the regenerative energy from the motor that is
causing the bus voltage to rise. This will reduce the risk of
an overhauling load causing an Overvolt Fault.

Parameter Number

288

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Enabled” 1

[Bus Limit En] must also be “Enabled”

[Load Loss Detect]

This parameter enables the function that detects an
indicated loss of load on the motor. A fault (F20) or alarm
condition will occur if [Torque Current] falls below [Load
Loss Level] for a time period greater than [Load Loss
Time].

Parameter Number

290

Parameter Type

Read and Write

Factory Default

“Disabled”

Units

Display Drive

“Disabled” 0

“Alarm” 1

Requires a value in [Load Loss Time]

“Fault” 2

Requires a value in [Load Loss Time]
Generates an F20 fault

Seconds

Hertz

Maximum Traverse (–)

Traverse

P-Jump

P-Jump (+)

P-Jump (–)

Output

Reference

Traverse Period

–20

0

10

20

30

40

50

60

20

40

Maximum Traverse (+)

Traverse Function