Chapter 4, Installation/wiring for plc control drives, Control and signal wiring – Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual

Page 39: Control and signal wiring –1, Chapter

Advertising
background image

Chapter

4

Installation/Wiring for PLC Control
Drives

This chapter provides the information you need to perform the control
and signal wiring for the PLC control version of the 1336 SPIDER
Drive. Refer to Chapter 2 for general installation and wiring.

Control and Signal Wiring

General Wiring Information

General requirements for analog and digital signal wire include:
stranded copper 0.750-0.283 mm

2

(18-22 AWG), twisted-pair, 100%

shield, 300V minimum insulation rating and a temperature rating
suitable for the application (not less than 60 degrees C.). Refer to
Table 4.A for terminal block specifications and Figure 4.1 for
locations.

Table 4.A
Control and Signal Terminal Block Specifications

1

Wire sizes given are maximum/minimum sizes that terminal block will accept - these are not
recommendations.Use Copper wire only. Wire gauge requirements and recommendations are based
on 75 degree C. Do not reduce wire gauge when using higher temperature wire.

Signal Connections

If the drive control connections are to be linked to an electronic
circuit or device, the common or 0V line should, if possible, be
grounded at the device (source) end only.

Important: The signal common (0V) of the drive is internally

connected to PE. User speed reference signals are
terminated to logic common. This puts the negative (or
common) side of these signals at earth ground potential.
Control schemes must be examined for possible conflicts
with this type of grounding scheme.

!

ATTENTION: The following information is merely a
guide for proper installation. The Allen-Bradley
Company cannot assume responsibility for the
compliance or the noncompliance to any code, national,
local or otherwise for the proper installation of this drive
or associated equipment. A hazard of personal injury
and/or equipment damage exists if codes are ignored
during installation.

Drive Catalog
Number

Max./Min. Wire Size

1

mm2 (AWG)

Screw
Size

Torque Range
N-m (lb.-in.)

Remove Insulation
mm (in.)

All

0.14-1.5 (28-16)

M2

0.22-0.25 (1.9-2.2) 9 (0.35)