Rockwell Automation 1336Z SPIDER - FRN 2.xxx-5.xxx User Manual
Page 165
Advertising
CE Conformity
C–3
Figure C.2
Typical Cabinet Layout
L1, L2, L3
U, V, W
PE
PE
M
G
5
4
3
2
1
U, V, W
Cabinet
Mounting Panel (must be conducting)
Inverter
Line Filter (if not integrated)
AC Input Line Choke (if not integrated)
AC Input Contactor
AC Input Fuses
Terminals
Cabinet Protection Earth Bus Bar
All wiring must be as
short as possible.
Unshielded input power wiring must
be bound together forming a triangle
(in cross section).
Unshielded output power wiring must
be bound together forming a triangle
(in cross section).
Input and output wiring must be
separated.
Power and signal leads inside the
cabinet must be physically separated.
1. Cable Bracket
2. Shield
3. Shielded 4-Wire Motor Cable
4. Shielded Signal Cable
5. EMC Tested Shielded Conduit Fitting