Feature Select

[Load Loss Level]

Sets the torque current level below which a load loss fault/
warning will occur. The value is expressed as a
percentage of programmed [Motor NP Amps].

Parameter Number

291

Parameter Type

Read and Write

Display Units / Drive Units

1 % / 4096 = 100%

Factory Default

0%

Minimum Value

0%

Maximum Value

100%

[Load Loss Time]

Sets the amount of time the drive [Torque Current] is
below [Load Loss Level], before the action set in [Load
Loss Detect] is taken.

Parameter Number

292

Parameter Type

Read and Write

Display Units / Units

1 Second / Seconds

Factory Default

0 Sec

Minimum Value

0 Sec

Maximum Value

30 Sec

[Bus Reg Level]

– Firmware 4.001 & later

[Max Bus Volts]

Sets the limit that the drive DC bus voltage can rise before
a fault occurs. When this parameter is set to the minimum
value, the drive DC bus voltage is limited to 110% of
nominal voltage. [Bus Limit En] must be “Enabled” for the
drive to limit the bus voltage. This setting is used to move
the trigger point for regulation above the turn-on point for
dynamic brake or regeneration packages.

Parameter Number

325

Parameter Type

Read and Write

Display Units / Drive Units

1 Volt / 4096 = Drive Rtd Volts

Factory Default

358/716/895 Volts

Minimum Value

358/716/895 Volts

Maximum Value

403/807/1009 Volts