Planning your panel layout, Establishing noise zones, Planning your panel layout -12 – Rockwell Automation 1394 SERCOS Interface Multi-Axis Motion Control System Installation Manual User Manual

Page 22: Establishing noise zones -12

Advertising
background image

Publication 1394-IN002B-EN-P — February 2004

1-12

Installing Your 1394 SERCOS Interface System

Planning Your Panel Layout

This section outlines the practices which minimize the possibility of
noise-related failures as they apply specifically to 1394 installations.
For more information on the concept of electrical noise reduction,
refer to System Design for Control of Electrical Noise Reference Manual
(publication GMC-RM001x-EN-P).

Establishing Noise Zones

Observe the following guidelines when laying out your panel (refer to
Figure 1.7 for zone locations).

The clean zone (C) is to the left of the 1394 and includes the

I/O wiring, feedback cable, and DC filter (grey wireway).

The dirty zone (D) is beneath and to the right of the 1394 (black
wireway) and includes the circuit breakers, transformer, 24V dc
power supply, contactors, AC line filter, and motor power cables.

The very dirty zone (VD) is limited to where the AC line (EMC)
filter VAC output jumpers over to the 1394. Shielded cable is
required only if the very dirty cables enter a wireway.

The SERCOS fiber-optic cables are immune to electrical noise, but
are relatively fragile and best run with other light weight cables.

Figure 1.7
Establishing Noise Zones

1

If I/O cable contains (dirty) relay wires, route wires in dirty wireway.

2

This is a clean 24V dc available for any device that may require it. The 24V enters the clean wireway and exits to
the left.

3

This is a dirty 24V dc available for motor brakes and contactors. The 24V enters the dirty wireway and exits to the
right.

(1)

C

D

D

VD

D

C

Status

DANGER

RISK OF ELECTRICAL SHOCK. HIGH VOLTAGE MAY

EXIST UP TO FIVE MINUTES AFTER REMOVING POWER.

SERCOS System Module

Route 24V dc I/O

Shielded Cable

Route Encoder/Analog/Registration

Shielded Cable

Dirty Wireway

Clean Wireway

Very dirty unshielded power connections
segregated (not in wireway)

24V Motor

Brake PS

Circuit

Breaker

XFMR

AC

Line Filter

DC

Filter

Contactors

1394 SERCOS interface System

3

2

I/O

1

and

Feedback Cables