Publication 1394-IN002B-EN-P — February 2004

1-16

Installing Your 1394 SERCOS Interface System

External Shunt Modules

Observe the following guidelines when mounting your external shunt
module (refer to Figure 1.9 and for an example).

Mount circuit components and wiring in the very dirty zone or in
an external shielded enclosure. Run shunt power and fan wiring
inside metal conduit to minimize the effects of EMI and RFI.

Mount resistors (other than metal-clad) in a shielded and
ventilated enclosure outside the cabinet.

Keep unshielded wiring as short as possible. Keep shunt wiring as
flat to the cabinet as possible.

Route thermal switch and fan wires separate from shunt power.

Figure 1.9
External Shunt Module Outside the Enclosure

C

C

D

D

VD

D

C

1394 Digital Servo Controller

300W Shunt Module

BULLETIN 1394 300W SHUNT MODULE

ALLEN-BRADLEY

FOR USE WITH 1394-SJT22-X SYSTEM MODULE

CAT.

PART

SER.

INPUT DC

INPUT AC

FOR FUSE REPLACEMENT USE:
BUSSMAN CAT. NO.

R

VD

Status

DANGER

RISK OF ELECTRICAL SHOCK. HIGH VOLTAGE MAY

EXIST UP TO FIVE MINUTES AFTER REMOVING POWER.

SERCOS System Module

(1)

Dirty Wireway

Clean Wireway

Customer-supplied

metal enclosure

150 mm (6.0 in.) of

clearance on all sides

of the shunt module

(minimum)

Enclosure

Shunt Power Wiring Methods:

Twisted pair in conduit (1st choice)

Shielded twisted pair (2nd choice)

Twisted pair, 2 twists per foot min. (3rd choice)

Metal conduit

(where required

by local code)

Route 24V dc I/O

Shielded Cable

Route Encoder/Analog/Registration

Shielded Cable

Very dirty shunt connections

segregated (not in wireway)

24V Motor

Brake PS

Circuit

Breaker

XFMR

AC

Line Filter

DC

Filter

Contactors

1394 SERCOS interface System

I/O and

Feedback Cables

Enclosure

Shunt thermal switch and