Input power conditioning, Input power conditioning -3 – Rockwell Automation 1394 SERCOS Interface Multi-Axis Motion Control System Installation Manual User Manual

Page 57

Advertising
background image

Publication 1394-IN002B-EN-P — February 2004

Connecting Your 1394 SERCOS Interface System

3-3

Input Power Conditioning

In most applications, you can connect the 1394 system module
directly to a three-phase, AC power line. However, if certain power
line conditions exist, the input power component can malfunction. If
either of the following is true, you can use a line reactor or isolation-
type transformer to reduce the possibility of this type of malfunction:

The AC line supplying the drive has power factor correction
capacitors.

The AC line frequently experiences transient power interruptions
or significant voltage spikes.

IMPORTANT

Line conditioning is not typically required. If you
have experienced power problems in the past on a
power distribution line, you may need to consider
input power conditioning.