Power wiring requirements are given in the tables below. Wire should
be copper with 75

°

C (167

°

F) minimum rating, per NFPA 79 unless

otherwise noted. Phasing of main input power is arbitrary and earth
ground connection is required for safe and proper operation.

1394 Power Wiring Requirements

1

The input power terminal designated PE is electrically common to the system module single point bond bar, so the
ground connection at PE is optional. However, the ground connection at the single point bond bar is mandatory.

2

105° C (221° F), 600V.

Note: Refer to the section Understanding External Shunt Connections

on page 3-34 for more information regarding the COL, INT, and
DC+ connections.

IMPORTANT

The National Electrical Code and local electrical
codes take precedence over the values and methods
provided.

Module

Description

Connects to
Terminals

Recommended
Wire Size
mm

2

(AWG)

Torque Value
Nm (lb-in.)

System Module
1394C-SJT05-D or

1394C-SJT10-D

Main Input Power

U, V, W, PE

1

6 (10)

0.56 - 0.62

(5.0 - 5.6)

Input Logic Power

W1, W2

4 (12)

Shunt Resistor
Connections

COL, INT, DC+

6 (10)

2

System Module
1394C-SJT22-D

Main Input Power

U, V, W, PE

1

10 (8)

2.21 - 2.66

(20.0 - 24.0)

Input Logic Power

W1, W2

4 (12)

External Shunt Module
Connections

DC+, COL

10 (8)

2

System Module

1394C-SJTxx-D

Ground

Single Point
Bond Bar

10 (8)

1.6 (14)

Drive System OK and
Brake Relay Circuits

Relay Outputs

0.2-4.0 (26-12)

0.56 - 0.62

(5.0 - 5.6)

Axis Module

1394C-AM03,

-AM04, and -AM07

Motor Power

U1, V1, W1,
and PE2

Motor power
cable depends
on motor/drive
combination,

6 (10) maximum

Ground PE1

6

(10)

Axis Module

1394C-AM50,

-AM75, -AM50-IH,
and -AM75-IH

Motor Power

U1, V1, W1,
and PE2

Motor power
cable depends
on motor/drive
combination,

10 (8) maximum

1.55 - 2.0

(14.0 - 18.0)

Ground

PE1

10 (8)

Axis Module

1394C-AMxx and

-AMxx-IH

Thermal Switch and
Brake Filter Circuits

TB1/TB2

0.2-4.0 (26-12)

0.56 - 0.62

(5.0 - 5.6)