Determining Your Type of
Input Power

Before you ground or wire your 1394 system you must determine the
type of power distribution system you will be connecting to for main
input power. The 1394 system is designed to operate in both
grounded and ungrounded environments.

Grounded Power Configuration

The grounded power configuration allows you to ground your three-
phase power at a neutral point. The 1394 system module has a factory
installed jumper configured for grounded power distribution. If you
determine that you have grounded power distribution in your plant
you do not need to modify your system.

Figure 3.1
Grounded Power Configuration

Note: The input power terminal designated PE is electrically common

to the system module single point bond bar.

Status

U

V

W

PE2

W1

V1

U1

DANGER

RISK OF ELECTRICAL SHOCK. HIGH VOLTAGE MAY

EXIST UP TO FIVE MINUTES AFTER REMOVING POWER.

SERCOS System Module

PE1

1326 or MP-Series
motor power cable

Cable clamp around shield

Bonded cabinet ground bus

Conduit/4-Wire Cable

Ground grid or

power distribution ground

System module

single point bond bar

Shield