Setting the ground jumper in 22 kw system modules, Figure 3.3 f, Figure 3.3 – Rockwell Automation 1394 SERCOS Interface Multi-Axis Motion Control System Installation Manual User Manual

Page 61: J4 j5 j6

Advertising
background image

Publication 1394-IN002B-EN-P — February 2004

Connecting Your 1394 SERCOS Interface System

3-7

Figure 3.3
Ground Jumper Locations for the 5 and 10 kW System Modules

Setting the Ground Jumper in 22 kW System Modules

This procedures applies to 1394C-SJT22-D system module. To set the
ground jumper for an ungrounded system:

1. Verify that all 24V logic and main input power has been removed

from the system.

2. Open the system module door.

3. Locate the ground jumper inside the system module (refer to

Figure 3.4 for jumper location).

4. Without removing the circuit board, unplug the jumper and move

it to the ungrounded power distribution position. Refer to Figure
3.5
for the jumper positions.

01

2

3

4 5 6

7

8

9

1 2 3

J4

J5

J6

Enable0

Home0

Reg0_Com

Reg0_1

Pos_Otrav0

Neg_Otrav0

I/O_Com

Reg0_2

AXIS 0

Enable3

Home3

Reg3_Com

Reg3_1

Pos_Otrav3

Neg_Otrav3

I/O_Com

Reg3_2

AXIS 3

Enable2

Home2

Reg2_Com

Reg2_1

Pos_Otrav2

Neg_Otrav2

I/O_Com

Reg2_2

AXIS 2

Enable1

Home1

Reg1_Com

Reg1_1

Pos_Otrav1

Neg_Otrav1

I/O_Com

Reg1_2

AXIS 1

1

5

8

4

1 5

8

4

1

5

8

4

1

5

8

4

OUTPUT 0

OUTPUT 1

OUTPUT 2

OUTPUT 3

DRIVE SYSTEM OK

RELAY OUTPUTS

1

DANGER

!

RISK OF ELECTRICAL SHOCK.

MORE THAN ONE
DISCONNECT SWITCH
MAY BE REQUIRED TO
DE-ENERGIZE THE
EQUIPMENT BEFORE
SERVICE.

ELECTRICAL SHOCK HAZARD
FROM ENERGY STROAGE
CAPACITORS.

VERIFY LOW VOLTAGE
DISCHARGE BEFORE
SERVICING.

SEE INSTRUCTIONAL MANUAL.

DANGER

!

1394 Digital Servo Controller

System Module

SERCOS interface

TM

10

- SERCOS

Base Address

x10

- Analog_Out_1
- Analog_Out_2
- Analog_Out_3
- Analog_Out_4
- Common
- N/C
- N/C
- N/C
- N/C

AXIS 0

AXIS 1

AXIS 2

AXIS 3 RELA

Y

OUTPUTS

SERCOS

Network Status

- SERCOS

Receive

- SERCOS

Transmit

OFF ON

Upper Control Board Screw

Lower Control Board Screw

Ground Jumper Terminals

1394C-SJTxx-D

(5 and 10 kW)

Ribbon

Cable

Connector

Side

Control Board

Screw

IMPORTANT

Do not remove circuit board from 1394 system
module.

Advertising