Jog stuck on alarm jog count alarm, Filler discharge alarms, Not ok to discharge alarm – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 38: Fig. 3-62 to jog again press start display, On alarm, 65 jog display/jog again

Advertising
background image

25

CHAPTER 3
Filler

FIG. 3-62 TO JOG AGAIN PRESS START DISPLAY

2.

The Jog sequence resumes from
where the Jog left off when it was
paused.

Jog Stuck On Alarm

- - - - - ALARM CONDITION - - - - -

After each jog the instrument goes to a
pause state (Jog OFF) for a pre-determined
period of time if the jog stops. In this state
it checks the weight to see if it is within
the target window. If it is the instrument
moves on to the next cycle. If it is not it
jogs again as long as the allowable number
of jogs has not been exceeded. If the Jog
does not stop the JOG STUCK ON
ALARM appears. (See Fig. 3-63)

FIG. 3-63 JOG STUCK ON ALARM

1.

Check to see why the gate valve or
feeder did not close or stop. Correct
the problem. Press on the Clear button
to clear the alarm.

2.

The instrument goes back to the
WAIT mode where it checks if the
weight is within the target window. If
it is still under the target window the
instrument begins another job cycle.

Jog Count Alarm

- - - - - ALARM CONDITION - - - - -

If the configured JOG sequences are com-
pleted and an UNDERFILL condition still
exists, a JOG count alarm appears telling

you that you have used up the JOGs for
this sequence. (See Fig. 3-64)

FIG. 3-64 JOG COUNT ALARM

1.

Press the Clear button to clear the
alarm.

2.

The JOG display reappears asking
you if you want to start the JOG
sequence again. (See Fig. 3-65)

FIG. 3-65 JOG DISPLAY/JOG AGAIN

3.

If you want the instrument to JOG
again, press the Start button to repeat
the JOG sequence.

4.

If you DO NOT want the instrument
to JOG again, press the Stop button.
The instrument goes to the Standby
Menu and does NOT complete any
more cycles.

Filler Discharge Alarms

Not OK to Discharge Alarm

- - - - - ALARM CONDITION - - - - -

If the OK to Discharge function is turned
on and the instrument does not see an OK
to Discharge, a Not OK to discharge alarm
appears. (See Fig. 3-66)

FIG. 3-66 NOT OK TO DISCHARGE ALARM