Slow feed on alarm – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 79

Advertising
background image

HI 3010 Filler/Dispenser/IBC

66

User Guide

No Slow Feed Alarm

- - - - - ALARM CONDITION - - - - -

If the Slow Dispense Gate valve or feeder
is not open or on at the time you want to
slow dispense, the NO SLOW FEED
alarm appears on the display. (See Fig. 5-
59)

FIG. 5-59 NO SLOW FEED ALARM

1.

Determine why the Slow IBC Dis-
pense Gate did not open and correct
the problem.

2.

Press the Clear button to clear the
alarm. The “RESUME DISPENS-
ING SLOW” display appears. (See
Fig. 5-60)

FIG. 5-60 RESUME DISPENSING DISPLAY

3.

Press the Start button to resume slow
dispensing.

NOTE:

At the beginning of a dispense in Dual speed/
simultaneous dispensing the instrument checks to
make sure that the instrument is dispensing
slowly before starting the Fast Dispense. If the
instrument is NOT dispensing slowly the NO
SLOW FEED ALARM appears. Clearing the
alarm returns the system to Standby Mode. Any
further cycles are not completed.

Slow Feed On Alarm

- - - - - ALARM CONDITION - - - - -

If the Slow Dispense Gate valve or feeder
does NOT close or shut off, the SLOW
FEED ON alarm appears on the display.
(See Fig. 5-61)

FIG. 5-61 SLOW FEED ON ALARM

1.

Determine why the Slow Feed is On
and correct the problem.

2.

Press the Clear button to clear the
alarm. The wait timer display appears.
(See Fig. 5-62)

FIG. 5-62 WAIT TIMER DISPLAY

Under dispense/Over dispense Alarms

- - - - - ALARM CONDITION - - - - -

If the weight is NOT within the target win-
dow and the JOG function is not turned
On, the dispense is not accepted in the wait
state and an UNDER DISPENSE or
OVER DISPENSE alarm appear depend-
ing on the weight dispensed. (See Figs. 5-
63 & 64)

FIG. 5-63 UNDERDISPENSE ALARM

FIG. 5-64 OVERDISPENSE ALARM