Refill off alarm display, Refill on alarm display, Not ok to dispense – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 55

Advertising
background image

HI 3010 Filler/Dispenser/IBC

42

User Guide

Refill Off Alarm

- - - - - ALARM CONDITION - - - - -

If the Refill gate, valve or feeder does not
open or start within a preset time period
when the refill is detected the REFILL
OFF ALARM appears. (See Fig. 4-46)

FIG. 4-46 REFILL OFF ALARM DISPLAY

1.

Determine why refill started and cor-
rect the problem.

2.

Press the clear button to the clear the
alarm. The dispenser returns to the
Standby or On display depending on
whether the refill was an initial or
start of cycle refill.

NOTE:

If the dispenser returns to the standby display you
must press start again.

Refill On Alarm

- - - - - ALARM CONDITION - - - - -

If the Refill gate, valve or feeder does not
close or stop within its programmed time
period, when the refill high weight is
detected or the refill exceeds the refill
timeout parameter the REFILL ON
ALARM appears. (See Fig. 4-47)

FIG. 4-47 REFILL ON ALARM DISPLAY

1.

Quickly determine why refill stopped
and correct the problem.

2.

Press the clear button to clear the
alarm. The dispenser returns to the
Standby or On display depending on
whether the refill was an initial or
start of cycle refill.

NOTE:

If the dispenser returns to the standby display you
must press start again.

Not OK to Dispense Alarm

- - - - - ALARM CONDITION - - - - -

If the function is turned on and it is NOT
OK TO DISPENSE, an alarm appears in
the display. (See Fig. 4-48)

FIG. 4-48 NOT OK TO DISPENSE

1.

The Operator needs to determine why
it is NOT OK TO DISPENSE by
checking for problems with the elec-
trical and /or mechanical systems.

2.

Once the problem has been fixed,
push the Clear button to clear the
Alarm. The Filler/Dispenser returns to
the standby mode waiting a Start com-
mand.

NOTE:

The OK to DISPENSE Timer has a preset time to
determine if it is OK to Dispense. If the OK to
Dispense times out, it means that the preset time
maybe too short for the process and the NOT OK
to DISPENSE Alarm appears with no real alarm
condition. You may need to reset the timer if it
appears that no electrical or mechanical reason
for the alarm is determined. The OK to DIS-
PENSE timer may be set incorrectly for your pro-
cess. See the HI 3010 Service Manual for
Instructions on setting the OK to DISPENSE
Timer

Lost OK to Dispense Alarm

- - - - - ALARM CONDITION - - - - -

During the dispensing process, conditions
may develop that cause the Filler/Dis-
penser to lose the OK to DISPENSE dur-
ing Fast Dispense or Slow Dispense.
When this occurs an alarm appears that
says LOST OK TO DISPENSE. (See Figs.
4-49 & 4-50)