Dispense timeout alarm, Jog alarms, Did not jog alarm – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 59: Fig. 4-67 accept dispense display, 71 did not jog alarm

Advertising
background image

HI 3010 Filler/Dispenser/IBC

46

User Guide

FIG. 4-66 ACCEPT DISPENSE DISPLAY

UNDERDISPENSE ALARM, press the
Clear button to clear the alarm, the Accept
the Dispense display appears. At this time
you can:

1.

Accept the dispense by pressing the
START button.

2.

If your system allows, physically add
some of the material until it meets the
target window requirements and then
press the START button.

3.

The instrument returns to the Waiting
On Display, repeats the motion check,
autotares and/or checks the OK to
Dispense processes and begins dis-
pense cycle number 2

Dispense Timeout Alarm

- - - - - ALARM CONDITION - - - - -

If this function is turned On, it times the
dispense cycle between the ON and WAIT
modes. If this time is exceeded the TIME-
OUT ALARM appears. (See Fig. 4-67)

FIG. 4-67 TIMEOUT ALARM

1.

Do a physical check of your system
looking for blockages or breaks and
make corrections as necessary.

2.

Press the Clear button to clear the
alarm. Depending on whether you are
operating single or dual speed and
when the Timeout occurred, one of
the following displays appears. (See
Figs. 4-68 & 69)

FIG. 4-68 RESUME DISPENSE FAST DISPLAY

FIG. 4-69 RESUME DISPENSE SLOW DISPLAY

3.

Press the Start button to resume the
fast or slow dispense.

4.

If the Stop button is pressed the
instrument will go to the Standby
Mode and not complete any more
requested cycles.

Jog Alarms

Did Not Jog Alarm

- - - - - ALARM CONDITION - - - - -

If the gate valve or feeder of the vessel or
come on the DID NOT JOG ALARM
appears on the display and the Filler/Dis-
penser is placed in a hold state. (See Fig.
4-70)

FIG. 4-70 DID NOT JOG ALARM

1.

Check to see why there was no Jog.
Correct the problem. Press on the
Clear button to clear the alarm. (See
Fig.4-71)