No fast feed alarm fast feed on alarm, Fast feed on alarm – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 78

Advertising
background image

65

CHAPTER 5
Operating Procedures/IBC Dispenser

1.

Press the Clear button to clear the
alarm then manually inspect the IBC
to determine if it is empty.

2.

If it is empty replace the IBC with a
full one.

3.

When the full IBC is in place, press
the Start button. The IBC dispenser
completes the dispense from where it
left off before the bag change.

NOTE:

If the IBC is not empty, fix the problem and press
the Start button once. The IBC dispenser com-
pletes the dispense from where it left off before
the bag change.

No Fast Feed Alarm

- - - - - ALARM CONDITION - - - - -

If the Fast Dispense Gate valve or feeder is
not open or on at the time you want to dis-
pense, the NO FAST FEED alarm appears
on the display. (See Fig. 5-54)

FIG. 5-54 NO FAST FEED ALARM

1.

Determine why you do not have Fast
Feed and correct the problem.

2.

Press the Clear button to clear the
alarm. The RESUME DISPENS-
ING? display appears, for single
speed or sequential IBC dispensing.
(See Fig. 5-55)

FIG. 5-55 RESUME DISPENSING FAST DISPLAY

3.

Press the Start button to resume dis-
pense. (See Fig. 5-56)

4.

In dual speed/simultaneous operation
press the Clear button to clear the

alarm. The RESUME DISPENSE
SLOW appears. (See Fig. 5-57)

FIG. 5-56 FAST DISPENSE ON

FIG. 5-57 RESUME DISPENSE SLOW

Fast Feed On Alarm

- - - - - ALARM CONDITION - - - - -

If the Fast Dispense Gate valve or feeder
does not close or shut off at the end of a
cycle, the FAST FEED ON alarm appears
on the display. (See Fig. 5-58)

FIG. 5-58 FAST FEED ON ALARM

1.

Determine why the Fast Feed is On
and correct the problem.

2.

Press the Clear button to clear the
alarm.

3.

If the weight is NOT within the target
window and you do not have the JOG
function on, the IBC dispense is
accepted and an UNDER DISPENSE
or OVER DISPENSE alarm will
appear depending on the weight dis-
pensed.