Test complete, Stable – Hardy HI 2151/30WC Single-Scale Controller User Manual

Page 134

Advertising
background image

HI 2151/30WC MANUAL

8-14

C - Guidelines for
Instabilities on
Formerly Operating
Systems

At the I.T. JUNCTION BOX

Remove and Replace

the load sensor(s) determined to be faulty.

If you are unable to isolate the instability:

Compare your results by testing the vessel when empty

and then re-testing under load.

GO TO B for additional system checks

OR

Contact Hardy Instruments

Customer Support

800-821-5831

TEST

COMPLETE

STABLE ?

Replace summing card

Re-install all load

sensors

YES

stable ?

YES

NO

YES

SYS_TST (cont.) REF_LS

This program checks individual Load

Sensors.

Press ENTER

Press: ENTER

To continue checking

load Sensors

Repeat for all load

Sensors

STABLE ?

C

Next

loadpoint

Record Load

Sensor data for

comparison. If

stable or not.

NO

NO