Installing the hi 2151/30wc in a panel -3, 2” rear panel clearance requirement -3 – Hardy HI 2151/30WC Single-Scale Controller User Manual

Page 33

Advertising
background image

Chapter 3 - Installation

3-3

Installing the HI 2151/
30WC in a Panel

Panel Cutout
Specifications

1. Enclosure Size Requirements.

Overall depth of the enclosure must be a minimum of 11.5" to allow
for the 2" clearance between the rear panel of the HI 2151/30WC
and the inside surface of the rear panel of the enclosure. (See Fig. 3-
1)

There must be a 1" clearance completely around the bezel
and other installed units.

FIG. 3-1 2” REAR PANEL CLEARANCE REQUIREMENT

2. Dimensions of the enclosure cutout (See Fig. 3-2)

5.75" ± .06 (146.05mm ±1.52) Wide

3.09" ± .06 (78.49mm ±1.52) High

All cutout surfaces must be deburred before installation of
the controller.

WARNING

DO NOT MOUNT THE HI 2151/30WC CONTROLLER NEAR A HIGH MAG-
NETIC FIELD OR HIGH VAC POWER SOURCE. TO DO SO WILL EFFECT
THE PERFORMANCE OF THE CONTROLLER AND MAY RESULT IN
PROPERTY DAMAGE.

Installing the HI
2151/30WC Panel
Mount

Step 1.

Ensure that all Electrostatic Discharge (ESD) precautions
have been taken before installation.

Step 2.

The controller comes with a NEMA 4 rated compression gas-
ket. Make sure the gasket is properly seated in the bezel
before installation.

2.0"

Front Panel

Bezel

Rear

Panel

Advertising