5-13

Analog Output
Menu Setup
Procedures

Step 1.

Press the 7/Option button. ROC appears.

Step 2.

Press the up arrow until Analog Output 1 ANAOUT1 or
Analog Output 2 ANAOUT2 is displayed.

Step 3.

Press the Enter button. ANLO appears.

Step 4.

Press Enter button.

Step 5.

Press -/Test/Clr button to clear the entry.

Step 6.

Use the numerical keypad to enter the value desired. (Enter (-
) for loss-in-weight systems.)

Step 7.

The value displayed will equal 4 milliamps, 0 milliamps, or0
volts, depending on which output and configuration is used.

Step 8.

Press the Enter button. A GOOD will momentarily appear and
AN HI appears.

Step 9.

Press the Enter button.

Step 10. Press -/Test/Clr button to clear the entry.

Step 11. Use the numerical key pad to enter the numerical value

desired. (Enter (-) for loss-in-weight systems.)

Step 12. The value displayed will equal 20 milliamps, 10 volts, or 5

volts, depending on which output and configuration is used.

Step 13. Set mode by pressing the MODE button until the cursor is

flashing under the desired option. Select from total, gross, net,
ROC, or peak. The default is gross.

Step 14. Press the Enter button. AN - LO re-appears.

Step 15. Press the Exit button. ANOUT re-appears.

Step 16. Press the Exit button again to return to the weight display.

NOTE:

Display may show an option other than "ROC", depending upon the option boards
installed.

NOTE:

Previously set numerical value will be displayed. "0" is the default.

NOTE:

Display momentarily flashes GOOD if value is a valid entry.

Setting the Rate of
Change Procedures

Step 1.

To select Rate of Change Mode: Push the MODE button until
the ROC LED indicator is lit

Step 2.

Press the 7/Option button. ROC appears.

Step 3.

Press the Enter button. UNITS appears.

Step 4.

Press the Enter button. U-SEC appears.

NOTE:

Previously set time value will be displayed. For this example, the time value will be
set to seconds.

Advertising