HI 2151/30WC MANUAL

5-14

Step 5.

Use the up

↑ or down arrows ↓ to select the appropriate mea-

surement of time (seconds U-SEC, minutes U-MIN, or hours
U-HR).

Step 6.

Press Enter button. BASE appears.

Step 7.

Press the Enter button.

Step 8.

Use the up or down arrows to select time base from one of the
following: 1, 2, 3, 4, 5, 6, 10, 12, 15, 30, 60, 120,240, 450,
900, or 1800.

Step 9.

Press the Enter button. The UNITS re-appears.

Step 10. Press the Exit button twice to return to the weight display.

NOTE:

Display may vary depending on which options were installed in your instrument. The
HI 2151/30WC will show the first available option, in this case, ROC.

TOTAL Setup
Procedures

Step 1.

Via the Calibration Menu, select the desired decimal point
position.

Step 2.

To add weight value to the Total Register: The current net
weight displayed will be added to the net weight accumulated
in the total register when the total remote function input is
detected (this is accomplished by providing a momentary
switch to the remote function connector between J2, Pin 8 and
J2, Pin 9 or 10.

Set Up for Profibus
Interface Card Option -
B12

See the Profibus Interface Option, Card Operation and Installation
Manual #0596-0231 for complete instructions.

Allen-Bradley Remote I/O
Option -B8

See the Allen-Bradley Remote I/O Installation and Operation Manual #
0596-0173 for complete instructions.