Carrier Streamline Scroll 69NT20-531-300 User Manual

Page 29

Advertising
background image

3-4

T-309

3.2.2 Operational Software (Function codes)

The Operational Software is the actual operation

programming of the controller which activates or

deactivates components in accordance with current unit

operating conditions and operator selected modes of

operation.

The programming is divided into function Codes. Some

of the codes are read only while the remaining codes

may be user configured. The value of the user

configurable codes can be assigned in accordance with

user desired mode of operation. A list of the function

codes is provided in Table 3-5.

To access the function codes, perform the following:

a. Press the CODE SELECT key, then press an arrow

key until the left window displays the desired code

number.

b. The right window will display the value of this item

for five seconds before returning to the normal dis-

play mode.

c. If a longer time is desired, press the ENTER key to

extend the time to 30 seconds.

3.3 MODES OF OPERATION

The Operational Software responds to various inputs.

These inputs come from the temperature and pressure

sensors, the temperature set point, the settings of the the

configuration variables and the function code

assignments. The action taken by the Operational

Software will change if any one of the inputs changes.

Overall interaction of the inputs is described as a

“mode” of operation. The modes of operation include,

perishable (chill) mode and frozen mode. Descriptions

of the controller interaction and modes of operation are

provided in the following sub paragraphs.

3.3.1 Temperature Control -- Perishable Mode

With configuration variable CnF26 (Heat Lockout

Temperature) set to --10_C the perishable mode of

operation is active with set points at or above --10_C

(+14_F). With the variable set to --5_C, the perishable

mode is active at or above --5_C (+23_F). Refer to

Table 3-4.

When in the perishable mode the controller maintains

the supply air temperature at set point, the SUPPLY

indicator light will be illuminated on the display module

and the default reading on the display window will be

the supply temperature sensor reading.

When the supply air temperature enters the in-range

temperature tolerance (as selected at function code

Cd30), the in-range light will energize.

3.3.2 Defrost Interval

Function code Cd27 may be operator set to initiate

defrost at intervals of 3, 6, 9, 12 or 24 hours. It may also

be set to OFF (no defrost). The factory default is 12

hours. (Refer to Table 3-5).

3.3.3 Failure Action

Function code Cd29 may be operator set to allow

continued operation in the event the control sensors are

reading out of range. The factory default is full system

shutdown. (Refer to Table 3-5).

3.3.4 Generator Protection

Function codes Cd31(Stagger Start, Offset Time) and

Cd32 (Current Limit) may be operator set to control

start up sequence of multiple units and operating current

draw. The factory default allows on demand starting (no

delay) of units and normal current draw. Refer to

Table 3-5.

3.3.5 Compressor High Temperature, Low Pres-

sure Protection.

The controller monitors compressor suction and

discharge temperatures and pressures. If the discharge

temperature exceeds a certain limit, the liquid injection

valve is opened to provide sufficient liquid refrigerant

flow into the economizer line to reduce the discharge

temperature. If the liquid injection is unable to reduce

the discharge temperature sufficiently and the

temperature exceeds the allowed limit, the compressor

will cycle off on a 3 minute timer. The compressor will

also cycle off in a similar manner if the suction pressure

falls below the allowed limit. Condenser and evaporator

fans continue to operate during the compressor off

cycle.

3.3.6 Perishable Mode -- Conventional

The unit is capable of maintaining supply air

temperature to within ¦0.25_C (¦0.5_F) of set point.

Supply air temperature is controlled by positioning of

the suction modulation valve (SMV), cycling of the

compressor and cycling of the heaters.
When cooling from a temperature that is more than

2.5_C (4.5_F) above set point, the system will be in the

perishable pull down mode. It will be in economized

operation with a target SMV position of 100% open.

However, pressure and current limit functions may

restrict the valve, if either exceeds the preset value.
Once set point is reached, the unit will transition to the

perishable steady state mode. This results in unloaded

operation with some restriction of the SMV. The SMV

will continue to close and restrict refrigerant flow until

the capacity of the unit and the load are balanced.
If the SMV is at minimum modulation, the controller

has determined that cooling is not required, or the

controller logic determines suction pressure is at the low

pressure limit, the unit will transition to the perishable

idle mode. The compressor is turned off and the

evaporator fans continue to run to circulate air

throughout the container. If temperature rises above set

point +0.2_C, the unit will transition back to the

perishable steady state mode
If the temperature drops to 0.5_C (0.9_F) below set

point, the unit will transition to the perishable heating

Advertising