Carrier Streamline Scroll 69NT20-531-300 User Manual

Page 52

Advertising
background image

3-27

T-309

Table 3-10 DataCORDER Alarm Indications

To Access: Press ALT. MODE key

Code No.

TITLE

DESCRIPTION

dAL70

Recorder Supply

Temperature Out of

Range

The supply recorder sensor reading is outside of the range of --50_C to

70_C (--58_F to +158_F) or, the probe check logic has determined there is

a fault with this sensor.

NOTE

The P5 Pre-Trip test must be run to inactivate the alarm.

dAL71

Recorder Return Tem-

perature Out of Range

The return recorder sensor reading is outside of the range of --50_C to

70_C (--58_F to +158_F) or, the probe check logic has determined there is

a fault with this sensor.

NOTE

The P5 Pre-Trip test must be run to inactivate the alarm.

dAL72-74 USDA Temperatures

1, 2, 3 Out of Range

The USDA probe temperature reading is sensed outside of --50 to 70

°C

(--58 to 158

°F) range.

dAL75

Cargo Probe 4 Out of

Range

The cargo probe temperature reading is outside of --50 to 70

°C (--58 to

158

°F) range.

dAL76, 77 Future Expansion

These alarms are for future expansion, and are not in use at this time.

dAL78-85 Network Data Point

1 -- 8 Out of Range

The network data point is outside of its specified range. The DataCORD-

ER is configured by default to record the supply and return recorder sen-

sors. The DataCORDER may be configured to record up to 8 additional

network data points. An alarm number (AL78 to AL85) is assigned to

each configured point. When an alarm occurs, the DataCORDER must be

interrogated to identify the data point assigned. When a humidity sensor is

installed, it is usually assigned to AL78.

dAL86

RTC Battery Low

The Real Time Clock (RTC) backup battery is too low to adequately

maintain the RTC reading.

dAL87

RTC Failure

An invalid date or time has been detected. This situation may be corrected

by changing the Real Time Clock (RTC) to a valid value using the Data-

View.

dAL88

DataCORDER

EEPROM Failure

A write of critical DataCORDER information to the EEPROM has failed.

dAL89

Flash Memory Error

An error has been detected in the process of writing daily data to the non-

volatile FLASH memory.

dAL90

Future Expansion

This alarm is for future expansion, and is not in use at this time.

dAL91

Alarm List Full

The DataCORDER alarm queue is determined to be full (eight alarms).