5-1

T-309

SECTION 5

TROUBLESHOOTING

CONDITION

POSSIBLE CAUSE

REMEDY/

REFERENCE

SECTION

5.1 UNIT WILL NOT START OR STARTS THEN STOPS

External power source OFF

Turn on

No power to unit

Start-Stop switch OFF or defective

Check

No power to unit

Circuit breaker tripped or OFF

Check

Circuit breaker OFF or defective

Check

Loss of control power

Control transformer defective

Replace

Loss of control power

Fuse (F3) blown

Check

Start-Stop switch OFF or defective

Check

Evaporator fan motor internal protector open

6.17

Condenser fan motor internal protector open

6.12

Compressor internal protector open

6.8

Component(s) Not Operating

High pressure switch open

5.7

Component(s) Not Operating

Heat termination thermostat open

Replace

Loss of communication with expansion module

Check Wiring

Malfunction of current sensor

Replace

Low line voltage

Check

Compressor hums, but does not Single phasing

Check

Compressor hums, but does not

start

Shorted or grounded motor windings

6.8

Compressor seized

6.8

5.2 UNIT OPERATES LONG OR CONTINUOUSLY IN COOLING

Container

Hot load

Normal

Container

Defective box insulation or air leak

Repair

Shortage of refrigerant

6.7.1

Evaporator coil covered with ice

5.6

Evaporator coil plugged with debris

6.15

Evaporator fan(s) rotating backwards

6.15/6.17

Defective evaporator fan motor/capacitor

6.18

Air bypass around evaporator coil

Check

Controller set too low

Reset

Refrigeration System

Compressor service valves or liquid line shutoff valve par-

tially closed

Open valves

completely

Dirty condenser

6.11

Compressor worn

6.8

Current limit (function code Cd32) set to wrong value

3.5.5

Suction modulation valve lost track of step count

Power cycle

Suction modulation valve malfunction

6.20

Economizer solenoid valve or TXV malfunction

6.14, 6.19

Unloader valve stuck open

6.19