Carrier Streamline Scroll 69NT20-531-300 User Manual

Page 32

Advertising
background image

3-7

T-309

e. “END” is displayed to indicate the end of the alarm

list if any alarms are active.

f. “CLEAr” is displayed if all alarms are inactive. The

alarm queue may than be cleared by pressing the EN-

TER key. The alarm list will clear and “

-- -- -- -- --

will be displayed.

3.5. UNIT PRE-TRIP DIAGNOSTICS

Pre--Trip Diagnostics is an independent controller

function which will suspend normal refrigeration

controller activities and provide preprogrammed test

routines. The test routines include Auto Mode testing,

which automatically preforms a pre programmed

sequenced of tests, or Manual Mode testing, which

allows the operator to select and run any of the

individual tests.

CAUTION

Pre-trip inspection should not be performed

with critical temperature cargoes in the con-

tainer.

CAUTION

When Pre-Trip key is pressed, economy, de-

humidification and bulb mode will be deac-

tivated. At the completion of Pre-Trip activi-

ty, economy, dehumidification and bulb

mode must be reactivated.

Testing may be initiated by use of the Key Pad or via

communication, but when initiated by communication

the controller will execute the entire battery of tests

(auto mode).
At the end of a pre-trip test, the message “P,” “rSLts”

(pretest results) will be displayed. Pressing the ENTER

key will allow the user to see the results for all subtests.

The results will be displayed as “PASS” or “FAIL” for

all the tests run to completion.
A detailed description of the pre-trip tests and test codes

is provided in Table 3-7. detailed operating instructions

are provided in paragraph 4.7.

3.6 DataCORDER
3.6.1 Description

The Carrier Transicold “DataCORDER,” software is

integrated into the controller and serves to eliminate the

temperature

recorder

and

paper

chart.

The

DataCORDER functions may be accessed by key pad

selections and viewed on the display module. The unit is

also fitted with interrogation connections (see

Figure 3- 1) which may be used with the Carrier

Transicold Data Reader to down load data. A personal

computer with Carrier Transicold Data View software

may also be used to download data and configure

settings. The DataCORDER consists of:

Configuration Software

Operational Software

Data Storage Memory

Real Time Clock (with internal battery backup)

Six thermistor inputs

Interrogation Connections

Power supply (battery pack).

The DataCORDER performs the following functions:
a. Logs data at 15, 30, 60 or 120 minute intervals and

stores two years’ of data (based on one hour interval).

b. Records and displays alarms on the display module.
c. Records results of pre--trip testing.
d. Records DataCORDER and temperature control soft-

ware generated data and events as follows:

Container ID Change
Software Upgrades
Alarm Activity
Battery Low (Battery Pack)
Data Retrieval
Defrost Start and End
Dehumidification Start and End
Power Loss (w/wo battery pack)
Power Up (w/wo battery pack)
Remote Probe Temperatures in the Container

(USDA Cold treatment and Cargo probe recording)
Return Air Temperature
Set Point Change
Supply Air Temperature
Real Time Clock Battery (Internal Battery) Replace-

ment
Real Time Clock Modification
Trip Start
ISO Trip Header (When entered via Interrogation

program)
Economy Mode Start and End
“Auto 2” Pre-Trip Start and End
Bulb Mode Start
Bulb Mode changes
Bulb Mode End
USDA Trip Comment
Humidification Start and End
USDA Probe Calibration

3.6.2 DataCORDER Software

The DataCORDER Software is subdivided into the

Configuration Software, Operational Software and the

Data Memory.

a. Operational Software

The Operational Software reads and interprets inputs

for use by the Configuration Software. The inputs are

labeled Function Codes. There are 35 functions (see

Table 3-8) which the operator may access to examine

the current input data or stored data. To access these

codes, do the following:
1 Press the ALT. MODE & CODE SELECT keys.
2 Press an arrow key until the left window displays the

desired code number. The right window will display

the value of this item for five seconds before return-

ing to the normal display mode.

3 If a longer time is desired, press the ENTER key to

extend the time to 30 seconds.