Table 3-9 DataCORDER Pre-Trip Result Records

Test

No.

TITLE

DATA

1-0

Heater On

Pass/Fail/Skip Result, Change in current for Phase A, B and C

1-1

Heater Off

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

2-0

Condenser Fan On

Pass/Fail/Skip Result, Water pressure switch (WPS) -- Open/Closed,

Change in currents for Phase A, B and C

2-1

Condenser Fan Off

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

3-0

Low Speed Evaporator Fan

On

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

3-1

Low Speed Evaporator Fan

On

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

4-0

High Speed Evaporator Fan

On

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

4-1

High Speed Evaporator Fan

On

Pass/Fail/Skip Result, Change in currents for Phase A, B and C

5-0

Supply/Return Probe Test

Pass/Fail/Skip Result, STS, RTS, SRS and RRS

5-1

Secondary Supply Probe Test

Pass/Fail/Skip

5-2

Secondary Return Probe Test

Pass/Fail/Skip

6-0

Discharge Thermistor Test

Pass/Fail/Skip

6-1

Suction Thermistor Test

Pass/Fail/Skip

6-2

Discharge Pressure Sensor

Test

Pass/Fail/Skip

6-3

Suction Pressure Sensor Test

Pass/Fail/Skip

6-4

Compressor Current Draw

Test

Pass/Fail/Skip

6-5

Suction Modulation valve Test Pass/Fail/Skip

6-6

Economizer Valve Test

Pass/Fail/Skip

6-7

Unloader Valve Test

Pass/Fail/Skip

7-0

High Pressure Switch Closed

Pass/Fail/Skip Result, AMBS, DPT or CPT (if equipped)

Input values that component opens

7-1

High Pressure Switch Open

Pass/Fail/Skip Result, STS, DPT or CPT (if equipped)

Input values that component closes

8-0

Perishable Mode Heat Test

Pass/Fail/Skip Result, STS, time it takes to heat to 16_C (60_F)

8-1

Perishable Mode Pull Down

Test

Pass/Fail/Skip Result, STS, time it takes to pull down to 0_C (32_F)

8-2

Perishable Mode Maintain

Test

Pass/Fail/Skip Result, Averaged DataCORDER supply temperature

(SRS) over last recording interval.

9-0

Defrost Test

Pass/Fail/Skip Result, DTS reading at end of test, line voltage, line

frequency, time in defrost.

10-0

Frozen Mode Heat Test

Pass/Fail/Skip Result, STS, time unit is in heat.

10-1

Frozen Mode Pull Down Test

Pass/Fail/Skip Result, STS, time to pull down unit to --17.8_C (0_F).

10-2

Frozen Mode Maintain Test

Pass/Fail/Skip Result, Averaged DataCORDER return temperature

(RRS) over last recording interval.