Table 3-6 Controller Alarm Indications (Sheet 1 of 4)

Code

No.

TITLE

DESCRIPTION

AL13 Expansion Module

Alarm 13 is triggered if the control module has lost communication with the ex-

pansion module for more than five minutes or communication fails within the

first 15 seconds on power up. This alarm triggers failure action C (evaporator fan

only) or D (all machinery off) of Function Code Cd29 if the unit has a perishable

set point. Failure action D (all machinery off) is triggered if the unit has a frozen

set point

AL14 Phase Sequence

Failure -- Electronic

Alarm 14 is triggered if the electronic phase detection system is unable to deter-

mine the correct phase relationship. DIRCHECK will be displayed while the

relationship is determined. If the system is unable to determine the proper rela-

tionship alarm 14 will remain active. Additiotnal information on phase detection

may be displayed at Function Code Cd41. If the right most digit of Code Cd41 is

3 or 4, this indicates incorrect motor or sensor wiring. If the right most digit is 5,

this indicates a failed current sensor assembly.

AL15 Loss Cooling

Future Expansion

AL16 Compressor Current

High

Alarm 16 is triggered if compressor current draw is 15% over calculated maxi-

mum for 10 minutes out of the last hour. The alarm is display only and will trig-

ger off when the compressor operates for one hour without over current.

AL17 Phase Sequence

Failure -- Pressure

Alarm 17 is triggered if a compressor start in both directions fails to generate

sufficient pressure differential. The controller will attempt restart every twenty

minutes and deactivate the alarm if successful. This alarm triggers failure action

C (evaporator fan only) or D (all machinery off) of Function Code Cd29 if the

unit has a perishable set point. Failure action D (all machinery off) is triggered if

the unit has a frozen set point

AL18 Discharge Pressure

High

Alarm 18 is triggered if discharge pressure is 10% over calculated maximum for

10 minutes within the last hour. The alarm is display only and will trigger off

when the compressor operates for one hour without overpressure.

AL19 Discharge Tempera-

ture High

Alarm 19 is triggered if discharge temperature exceeds 135_C (275_F) for 10

minutes within the last hour. The alarm is display only and will trigger off when

the compressor operates for one hour without over temperature.

AL20 Control Circuit Fuse

Open (24 vac)

Alarm 20 is triggered by control power fuse (F3) opening and will cause the soft-

ware shutdown of all control units. This alarm will remain active until the fuse is

replaced.

AL21 Micro Circuit Fuse

Open (18 vac)

Alarm 21 is triggered by one of the fuses (F1/F2) being opened on 18 volts AC

power supply to the Controller. The suction modulation valve (SMV) will be

opened and current limiting is halted. Temperature control will be maintained by

cycling the compressor.

AL22 Evaporator Fan Mo-

tor Safety

Alarm 22 responds to the evaporator motor internal protectors. The alarm is trig-

gered by opening of either internal protector. It will disable all control units until

the motor protector resets and the unit is power cycled.

AL23 Loss of Phase B

Alarm 23 is triggered if low current draw is detected on phase B and IPCP, HPS

or IPEM is not tripped. If the compressor should be running, the controller will

initiate a start up every five minutes and trigger off if current reappears. If the

evaporator fan motors only should be running, the alarm will trigger off is cur-

rent reappears. This alarm triggers failure action C (evaporator fan only) or D

(all machinery off) of Function Code Cd29 if the unit has a perishable set point.

Failure action D (all machinery off) is triggered if the unit has a frozen set point

AL24 Compressor Motor

Safety

Alarm 24 is triggered when compressor is not drawing any current. It also trig-

gers failure action ”C” or ”D” set by function Code 29 for perishable setpoint, or

”D” for frozen setpoint. This alarm will remain active until compressor draws

current.