Carrier Streamline Scroll 69NT20-531-300 User Manual

Page 64

Advertising
background image

5-5

T-309

CONDITION

POSSIBLE CAUSE

REMEDY/

REFERENCE

SECTION

5.14 COMPRESSOR OPERATING IN REVERSE

CAUTION

Allowing the scroll compressor to operate in reverse for more than two minutes will result in internal

compressor damage. Turn the start--stop switch OFF immediately.

Incorrect wiring of compressor

Electrical

Incorrect wiring of compressor contactor(s)

Check

Electrical

Incorrect wiring of current sensor

Check

5.15 ABNORMAL TEMPERATURES

Discharge temperature sensor drifting high

Replace

Failed economizer, TXV or solenoid valve

Replace

High discharge temperature

Plugged economizer, TXV or solenoid valve

Replace

High discharge temperature

Loose or insufficiently clamped sensor

Replace

Failed liquid injection solenoid valve

Replace

Low suction temperature

Discharge temperature sensor drifting low

Replace

Low suction temperature

Loose or insufficiently clamped sensor

Replace

5.16 ABNORMAL CURRENTS

Unit reads abnormal currents

Current sensor wiring

Check