6-4

T-309

a. Remove all refrigerant using a refrigerant recovery

system.

b. The recommended method to evacuate and dehydrate

the system is to connect evacuation hoses at the com-

pressor suction, compressor economizer and liquid

line service valve (see Figure 6-5). Be sure the ser-

vice hoses are suited for evacuation purposes.

c. The area between the suction modulating valve and

evaporator expansion valve may not be open to the

access valves. To ensure evacuation of this area,

check that the suction modulating valve is more than

10% open at controller function code Cd01. If re-

quired, the suction modulating valve may be opened

by use of the controller function code Cd41 valve

override control. If power is not available to open the

valve, the area may be evacuated by connecting an

additional hose at the low side access valve (item 11,

Figure 2-2).

d. Test the evacuation setup for leaks by backseating the

unit service valves and drawing a deep vacuum with

the vacuum pump and gauge valves open. Shut off the

pump and check to see if the vacuum holds. Repair

leaks if necessary.

e. Midseat the refrigerant system service valves.
f. Open the vacuum pump and electronic vacuum gauge

valves, if they are not already open. Start the vacuum

pump. Evacuate unit until the electronic vacuum

gauge indicates 2000 microns. Close the electronic

vacuum gauge and vacuum pump valves. Shut off the

vacuum pump. Wait a few minutes to be sure the vac-

uum holds.

g. Break the vacuum with clean dry refrigerant 134a

gas. Raise system pressure to approximately 0.2 kg/

cm@ (2 psig), monitoring it with the compound

gauge.

h. Remove refrigerant using a refrigerant recovery sys-

tem.

i. Repeat steps f.and g. one time.
j. Remove the copper tubing and change the filter-drier.

Evacuate unit to 500 microns. Close the electronic

vacuum gauge and vacuum pump valves. Shut off the

vacuum pump. Wait five minutes to see if vacuum

holds. This procedure checks for residual moisture

and/or leaks.

k. With a vacuum still in the unit, the refrigerant charge

may be drawn into the system from a refrigerant con-

tainer on weight scales. Continue to paragraph 6.7

6

4

5

7

D

S

10

1

2

3

8

9

1. Receiver or Water

Cooled Condenser

2. Compressor

3. Discharge Service

Valve

4. Economizer Service

Valve

5. Suction Service Valve

6. Vacuum Pump

7. Electronic Vacuum

Gauge

8. Manifold Gauge Set

9. Refrigerant Cylinder

10. Reclaimer

Figure 6-6. Compressor Service Connections

6.6.4 Procedure - Partial System

a. If the refrigerant charge has been removed from the

compressor for service, evacuate only the compressor

by connecting the evacuation set--up at the compres-

sor service valves. (See Figure 6-6.) Follow evacua-

tion procedures of the preceding paragraph except

leave compressor service valves frontseated until

evacuation is completed.

b. If refrigerant charge has been removed from the low

side only, evacuate the low side by connecting the

evacuation set--up at the compressor suction and

economizer service valves and the liquid service

valve except leave the service valves frontseated until

evacuation is completed.

c. Once evacuation has been completed and the pump

has been isolated, fully backseat the service valves to

isolate the service connections and then continue

with checking and, if required, adding refrigerant in

accordance with normal procedures