Carrier Streamline Scroll 69NT20-531-300 User Manual

Page 43

Advertising
background image

3-18

T-309

Table 3-6 Controller Alarm Indications (Sheet 2 of 4)

AL25 Condenser Fan Mo-

tor Safety

Alarm 25 is triggered by the opening of the condenser motor internal protector

and will disable all control units except for the evaporator fans. This alarm will

remain active until the motor protector resets. This alarm triggers failure action

C (evaporator fan only) or D (all machinery off) of Function Code Cd29 if the

unit has a perishable set point. Failure action D (all machinery off) is triggered if

the unit has a frozen set point

AL26

All Supply and Re-

turn temperature

Control Sensors

Failure

Alarm 26 is triggered if the Controller determines that all of the control sensors

are out-of-range. This can occur for box temperatures outside the range of --50_C

to +70_C (--58_F to +158_F). This alarm triggers the failure action code set by

Function Code Cd29.

AL27 A/D Accuracy Fail-

ure

The Controller has a built-in Analog to Digital (A-D) converter, used to convert

analog readings (i.e. temperature sensors, current sensors, etc.) to digital read-

ings. The Controller continuously performs calibration tests on the A-D con-

verter. If the A-D converter fails to calibrate for 30 consecutive seconds, this

alarm is activated.This alarm will be inactivated as soon as the A-D converter

calibrates.

AL28 Low Suction Pres-

sure

Alarm 28 is triggered if suction pressure is below 2 psia and alarm 66 (Suction

Pressure Transducer Failure) is not active. This alarm will be inactivated when

suction pressure rises above 2 psia for three continuous minutes. This alarm trig-

gers failure action C (evaporator fan only) or D (all machinery off) as determined

by User Selectable Failure Response if the unit has a perishable set point; Failure

action D (all machinery off) if the unit has a frozen set point. Reset SMV.

AL51 Alarm List Failure

During start-up diagnostics, the EEPROM is examined to determine validity of

its contents. This is done by testing the set point and the alarm list. If the con-

tents are invalid, Alarm 51 is activated. During control processing, any operation

involving alarm list activity that results in an error will cause Alarm 51 to be ac-

tivated. Alarm 51 is a “display only” alarm and is not written into the alarm list.

Pressing the ENTER key when “CLEAr” is displayed will result in an attempt to

clear the alarm list. If that action is successful (all alarms are inactive), Alarm 51

will be reset.

AL52 Alarm List Full

Alarm 52 is activated whenever the alarm list is determined to be full; at start-up

or after recording an alarm in the list. Alarm 52 is displayed, but is not recorded

in the alarm list. This alarm can be reset by clearing the alarm list. This can be

done only if all alarms written in the list are inactive.

AL53 Battery Pack Failure

Alarm 53 is caused by the battery pack charge being too low to provide sufficient

power for battery-backed recording. Renew replaceable batteries. If this alarm

occurs on start up, allow a unit fitted with rechargeable batteries to operate for up

to 24 hours to charge rechargeable batteries sufficiently to deactivate the alarm

AL54

Primary Supply

Temperature Sensor

Failure (STS)

Alarm 54 is activated by an invalid primary supply temperature sensor reading

that is sensed outside the range of --50 to +70_C (--58_F to +158_F) or if the

probe check logic has determined there is a fault with this sensor. If Alarm 54 is

activated and the primary supply is the control sensor, the secondary supply sen-

sor will be used for control if the unit is so equipped. If the unit does not have a

secondary supply temperature sensor, and AL54 is activated, the primary return

sensor reading, minus 2_C will be used for control.

NOTE

The P5 Pre-Trip test must be run to inactivate the alarm

AL55 DataCORDER

Failure

This alarm activates to indicate the DataCORDER has a software failure. To

clear this alarm, reconfigure the unit to the current model number. This failure

may be the result of a voltage dip in access of 25%.

Advertising