Carrier Streamline Scroll 69NT20-531-300 User Manual

Page 45

Advertising
background image

3-20

T-309

Table 3-6 Controller Alarm Indications (Sheet 4 of 4)

NOTE

If the Controller is configured for four probes without a DataCORDER, the DataCORDER alarms AL70

and AL71 will be processed as Controller alarms AL70 and AL71. Refer to Table 3-10.

The Controller performs self-check routines. if an internal failure occurs, an

“ERR” alarm will appear on the display. This is an indication the Controller

needs to be replaced.
ERROR

DESCRIPTION

ERR 0 -- RAM failure

Indicates that the Controller working memory has

failed.

ERR Internal

Microprocessor

EER 1 -- Program

Memory failure

Indicates a problem with the Controller program.

ERR

#

Microprocessor

Failure

EER 2 -- Watchdog

time--out

The Controller program has entered a mode whereby

the Controller program has stopped executing.

EER 3 -- On board timer

failure

The on board timers are no longer operational.

Timed items such as; defrost, etc. may not work.

EER 4 -- Internal counter

failure

Internal multi-purpose counters have failed. These

counters are used for timers and other items.

EER 5 -- A-D failure

The Controller’s Analog to Digital (A-D) converter

has failed.

Entr

StPt

Enter Setpoint

(Press Arrow &

Enter)

The Controller is prompting the operator to enter a set point.

LO

Low Main Voltage

(Function Codes

Cd27--38 disabled

and NO alarm

stored.)

This message will be alternately displayed with the set point whenever the sup-

ply voltage is less than 75% of its proper value.