3-19

T-309

Table 3-6 Controller Alarm Indications (Sheet 3 of 4)

AL56

Primary Return

Temperature Sensor

Failure (RTS)

Alarm 56 is activated by an invalid primary return temperature sensor reading

that is outside the range of --50 to +70_C (--58_F to +158_F). If Alarm 56 is acti-

vated and the primary return is the control sensor, the secondary return sensor

will be used for control if the unit is so equipped. If the unit is not equipped with

a secondary return temperature sensor or it fails, the primary supply sensor will

be used for control.

NOTE

The P5 Pre-Trip test must be run to inactivate the alarm.

AL57 Ambient Tempera-

ture Sensor Failure

Alarm 57 is triggered by an ambient temperature reading outside the valid range

from --50_C (--58_F) to +70_C (+158_F).

AL58 Compressor High

Pressure Safety

Alarm 58 is triggered when the compressor high discharge pressure safety switch

remains open for at least one minute. This alarm will remain active until the pres-

sure switch resets, at which time the compressor will restart.

AL59 Heat Termination

Thermostat

Alarm 59 is triggered by the opening of the heat termination thermostat and will

result in the disabling of the heater. This alarm will remain active until the ther-

mostat resets.

AL60 Defrost Temperature

Sensor Failure

Alarm 60 is an indication of a probable failure of the defrost temperature sensor

(DTS). It is triggered by the opening of the heat termination thermostat (HTT) or

the failure of the DTS to go above set point within two hours of defrost initia-

tion. After one-half hour with a frozen range set point, or one-half hour of contin-

uous compressor run time, if the return air falls below 7_C (45_F), the Controller

checks to ensure the DTS reading has dropped to 10_C or below. If not, a DTS

failure alarm is given and the defrost mode is operated using the return tempera-

ture sensor. The defrost mode will be terminated after one hour by the Controller.

AL61 Heaters Failure

Alarm 61 is triggered by detection of improper amperage resulting from heater

activation or deactivation. Each phase of the power source is checked for proper

amperage.This alarm is a display alarm with no resulting failure action, and will

be reset by a proper amp draw of the heater.

AL62 Compressor Circuit

Failure

Alarm 62 is triggered by improper current draw increase (or decrease) resulting

from compressor turn on (or off). The compressor is expected to draw a mini-

mum of 2 amps; failure to do so will activate the alarm. This is a display alarm

with no associated failure action and will be reset by a proper amp draw of the

compressor.

AL63 Current Over Limit

Alarm 63 is triggered by the current limiting system. If the compressor is ON

and current limiting procedures cannot maintain a current level below the user

selected limit, the current limit alarm is activated. This alarm is a display alarm

and is inactivated by power cycling the unit, changing the current limit via the

code select Cd32, or if the current decreases below the activation level.

AL64 Discharge Tempera-

ture Over Limit

Alarm 64 is triggered if the discharge temperature sensed is outside the range of

--60_C (--76_F) to 175_C (347_F), or if the sensor is out of range. This is a dis-

play alarm and has no associated failure action.

AL65 Discharge Pressure

Transducer Failure

Alarm 65 is triggered if a compressor discharge transducer is out of range. This is

a display alarm and has no associated failure action.

AL66 Suction Pressure

Transducer Failure

Alarm 66 is triggered if a suction pressure transducer is out of range. This is a

display alarm and has no associated failure action.

AL67 Humidity Sensor

Failure

Alarm 67 is triggered by a humidity sensor reading outside the valid range of 0%

to 100% relative humidity. If alarm AL67 is triggered when the dehumidification

mode is activated, then the dehumidification mode will be deactivated.

AL69 Suction Temperature

Sensor Failure

Alarm 69 is triggered by a suction temperature sensor reading outside the valid

range of --60_C (--76_F) to 150_C (302_F). This is a display alarm and has no

associated failure action.