Carrier Streamline Scroll 69NT20-531-300 User Manual

Page 66

Advertising
background image

6-2

T-309

system can be charged. Oil can also be added to the

system.
A R-134a manifold gauge/hose set with self-sealing

hoses (see Figure 6-4) is required for service of the

models covered within this manual. The manifold

gauge/hose set is available from Carrier Transicold.

(Carrier Transicold P/N 07-00294-00, which includes

items 1 through 6, Figure 6-4.) To perform service using

the manifold gage/hose set, do the following:
a. Preparing Manifold Gauge/Hose Set For Use
1. If the manifold gauge/hose set is new or was exposed

to the atmosphere it will need to be evacuated to

remove contaminants and air as follows:

2. Back seat (turn counterclockwise )both field service

couplings (see Figure 6-4) and midseat both hand

valves.

3. Connect the yellow hose to a vacuum pump and re-

frigerant 134a cylinder.

OPENED
(Backseated )
HAND VALVE

CLOSED

(Frontseated)

HAND VALVE

SUCTION
PRESSURE
GAUGE

DISCHARGE
PRESSURE
GAUGE

To Low Side
Access Valve

To High Side
Access Valve

Red Knob

Blue Knob

1

4

3

YELLOW

2

4

5

6

3

RED

3

BLUE

2

1. Manifold Gauge Set

2. Hose Fitting (0.5-16 Acme)

3. Refrigeration and/or Evacuation Hose

.

(SAE J2196/R-134a)

4. Hose Fitting w/O-ring (M14 x 1.5)

5. High Side Field Service Coupling

6. Low Side Field Service Coupling

Figure 6-4 R-134a Manifold Gauge/Hose Set

7. Evacuate to 10 inches of vacuum and then charge

with R-134a to a slightly positive pressure of 0.1 kg/

cm@ (1.0 psig).

8. Front seat both manifold gauge set valves and dis-

connect from cylinder. The gauge set is now ready

for use.

b. Connecting Manifold Gauge/Hose Set
To connect the manifold gauge/hose set for reading

pressures, do the following:
1. Remove service valve stem cap and check to make

sure it is backseated. Remove access valve cap.

(See

Figure 6-1)

2. Connect the field service coupling (see Figure 6-4)

to the access valve.

3. Turn the field service coupling knob clockwise,

which will open the system to the gauge set.

4. To read system pressures: slightly midseat the ser-

vice valve.

5. Repeat the procedure to connect the other side of the

gauge set.

CAUTION

To prevent trapping liquid refrigerant in the

manifold gauge set be sure set is brought to

suction pressure before disconnecting.

c. Removing the Manifold Gauge Set
1. While the compressor is still ON, backseat the high

side service valve.

2. Midseat both hand valves on the manifold gauge set

and allow the pressure in the manifold gauge set to

be drawn down to low side pressure. This returns any

liquid that may be in the high side hose to the system.

3. Backseat the low side service valve. Backseat both

field service couplings and frontseat both manifold

set valves. Remove the couplings from the access

valves.

4. Install both service valve stem caps and service port

caps (finger-tight only).

6.4 PUMPING THE UNIT DOWN

To service the filter-drier, economizer, expansion

valves, moisture-liquid indicator, suction modulation

valve, economizer solenoid valve, unloader solenoid

valve or evaporator coil, pump the refrigerant into the

high side as follows:

CAUTION

The scroll compressor achieves low suction

pressure very quickly. Do not operate the

compressor in a deep vacuum, internal dam-

age will result.

a. Attach manifold gauge set to the compressor suction

and discharge service valves. Refer to paragraph 6.3.

b. Start the unit and run in the frozen mode (controller

set below --10

°C) for 10 to 15 minutes.

c. Check function code Cd21 (refer to paragraph 3.2.2).

The economizer solenoid valve should be open. If

not, continue to run until the valve opens.

d. Frontseat the oil return service valve then, frontseat

the liquid line service valve. Place start-stop switch in

the OFF position when the suction reaches a positive

pressure of 0.1 kg/cm@ (1.0 psig).

e. Frontseat the economizer service valve and then

frontseat the suction and discharge service valves.

The refrigerant will be trapped between the compres-

sor suction service valve and the liquid line valve.

f. Before opening up any part of the system, a slight

positive pressure should be indicated on the pressure