Carrier Streamline Scroll 69NT20-531-300 User Manual

Page 39

Advertising
background image

3-14

T-309

Table 3-5 Controller Function Codes (Sheet 1 of 3)

Code

No.

TITLE

DESCRIPTION

Note: If the function is not applicable, the display will read “-- -- -- -- --”

Display Only Functions

Cd01 Suction Modulation

Valve Opening (%)

Displays the SMV percent open. The right display reads 100% when the valve is

fully open. The valve will usually be at 10% on start up of the unit except in very

high ambient temperatures.

Cd02 Not Applicable

Not used

Cd03 Compressor Motor

Current

The current sensor measures current draw in lines L1 & L2 by all of the high

voltage components. It also measures current draw in compressor motor leg T3.

The compressor leg T3 current is displayed.

Cd04

Cd05

Cd06

Line Current,

Phase A

Line Current,

Phase B

Line Current,

Phase C

The current sensor measures current on two legs. The third unmeasured leg is cal-

culated based on a current algorithm. The current measured is used for control

and diagnostic purposes. For control processing, the highest of the Phase A and B

current values is used for current limiting purposes. For diagnostic processing,

the current draws are used to monitor component energization.. Whenever a heat-

er or a motor is turned ON or OFF, the current draw increase/reduction for that

activity is measured. The current draw is then tested to determine if it falls within

the expected range of values for the component. Failure of this test will result in a

pre-trip failure or a control alarm indication.

Cd07 Main Power Voltage The main supply voltage is displayed.

Cd08 Main Power Fre-

quency

The value of the main power frequency is displayed in Hertz. The frequency dis-

played will be halved if either fuse F1 or F2 is bad (alarm code AL21).

Cd09 Ambient Tempera-

ture

The ambient sensor reading is displayed.

Cd10 Compressor Suction

Temperature

Compressor suction temperature sensor reading is displayed.

Cd11 Compressor Dis-

charge Temperature

Compressor discharge temperature sensor reading is displayed.

Cd12 Compressor Suction

Pressure

Compressor suction pressure transducer reading is displayed.

Cd13 Not Applicable

Not used

Cd14 Compressor Dis-

charge Pressure

Compressor discharge pressure transducer reading is displayed.

Cd15 Unloader Valve

The status of the valve is displayed (Open - Closed).

Cd16 Compressor Motor

Hour Meter

Records total hours of compressor run time. Total hours are recorded in incre-

ments of 10 hours (i.e., 3000 hours is displayed as 300).

Cd17 Relative Humidity

(%)

Humidity sensor reading is displayed. This code displays the relative humidity, as

a percent value.

Cd18 Software Revision # The software revision number is displayed.

Cd19 Battery Check

This code checks the Controller/DataCORDER battery pack. While the test is

running, “btest” will flash on the right display, followed by the result. “PASS”

will be displayed for battery voltages greater than 7.0 volts. “FAIL” will be dis-

played for battery voltages between 4.5 and 7.0 volts, and “

-- -- -- -- --” will be

displayed for battery voltages less than 4.5 volts. After the result is displayed for

four seconds, “btest” will again be displayed, and the user may continue to scroll

through the various codes.

Cd20 Config/Model #

This code indicates the dash number of the model for which the Controller is con-

figured (i.e., if the unit is a 69NT40-531-100, the display will show “31100”).

Cd21 Economizer Valve

The status of the valve is displayed (Open - Closed).