Carrier Streamline Scroll 69NT20-531-300 User Manual

Page 67

Advertising
background image

6-3

T-309

gauge. If a vacuum is indicated, emit refrigerant by

cracking the liquid line valve momentarily to build up

a slight positive pressure.

g. When opening up the refrigerant system, certain parts

may frost. Allow the part to warm to ambient temper-

ature before dismantling. This avoids internal con-

densation which puts moisture in the system.

h. After repairs have been made, be sure to perform a

refrigerant leak check (refer to paragraph 6.5), and

evacuate and dehydrate the low side (refer to para-

graph 6.6).

i. Check refrigerant charge (refer to paragraph 6.7).

6.5 REFRIGERANT LEAK CHECKING

WARNING

Never use air for leak testing. It has been

determined that pressurized, air-rich mix-

tures of refrigerants and air can undergo

combustion when exposed to an ignition

source.

a. The recommended procedure for finding leaks in a

system is with a R-134a electronic leak detector. Test-

ing joints with soapsuds is satisfactory only for locat-

ing large leaks.

b. If the system is without refrigerant, charge the system

with refrigerant 134a to build up pressure between

2.1 to 3.5 kg/cm@ (30 to 50 psig). To ensure complete

pressurization of the system, refrigerant should be

charged at the compressor suction and economizer

service valves and the liquid line service valve. Also,

the area between the suction modulating valve and

evaporator expansion valve may not be open to these

charging points. Pressure between these components

may be checked at the low side access valve (item 11,

Figure 2-2) or by checking that the suction modulat-

ing valve is more than 10% open at controller func-

tion code Cd01. The suction modulating valve may

be opened by use of the controller function code Cd41

valve override control (refer to paragraph 6.19). Re-

move refrigerant cylinder and leak-check all connec-

tions.

NOTE

Only refrigerant 134a should be used to pres-
surize the system. Any other gas or vapor will
contaminate the system, which will require

additional purging and evacuation of the sys-
tem.

c. If required, remove refrigerant using a refrigerant

recovery system and repair any leaks.

d. Evacuate and dehydrate the unit. (Refer to paragraph

6.6.)

e. Charge unit per paragraph 6.7.

6.6 EVACUATION AND DEHYDRATION
6.6.1 General

Moisture is the deadly enemy of refrigeration systems.

The presence of moisture in a refrigeration system can

have many undesirable effects. The most common are

copper plating, acid sludge formation, “freezing-up” of

metering devices by free water, and formation of acids,

resulting in metal corrosion.

6.6.2 Preparation

a. Evacuate and dehydrate only after pressure leak test.

(Refer to paragraph 6.5.)

b. Essential tools to properly evacuate and dehydrate

any system include a vacuum pump (8 m

3

/hr = 5 cfm

volume displacement) and an electronic vacuum

gauge. (The pump is available from Carrier Trans-

icold, P/N 07-00176-11.)

c. If possible, keep the ambient temperature above

15.6_C (60_F) to speed evaporation of moisture. If

the ambient temperature is lower than 15.6_C

(60_F), ice might form before moisture removal is

complete. Heat lamps or alternate sources of heat may

be used to raise the system temperature.

d. Additional time may be saved during a complete sys-

tem pump down by replaceing the filter-drier with a

section of copper tubing and the appropriate fittings.

Installation of a new drier may be performed during

the charging procedure.

6

4

5

D

S

2

3

11

9

10

1

7

8

1. Liquid Service Valve

2. Receiver or Water

Cooled Condenser

3. Compressor

4. Discharge Service

Valve

5. Economizer Service

Valve

6. Suction Service Valve

7. Vacuum Pump

8. Electronic Vacuum

Gauge

9. Manifold Gauge Set

10. Refrigerant Cylinder

11. Reclaimer

Figure 6-5. Refrigeration System Service

Connections

6.6.3 Procedure - Complete system

Advertising