7 unit accuracy, 8 environmental conditions, Unit – CIRCUTOR AR6 Series User Manual

Page 15: Accuracy, Environmental, Conditions

Advertising
background image

AR6 portable network analyzer

User Manual

Page 15 of 69

Permanent overvoltage

1,000 V

RMS

Transitory overvoltage <1 s

2,500 Vpeak

Absolute maximum voltage

6 kV

Consumption

≤0.04 VA

Maximum voltage in the voltage measurement circuit

1000 V CAT III / 600 V CAT IV for elevations below 2000 m.

1000 V CAT II / 600 V CAT III / 300 V CAT IV for above 2000 m

4.7

UNIT ACCURACY

Variable

Resolution

Accuracy

Margin

Currents * (2 V input)

0.1 mA

± 0.5%

10% … 120% of In

Voltage

0.01 V

± 0.5%

20% … 120% of Un

Active power

0.1 W

± 1%

Reactive power

0.1 VAr

± 1%

Apparent power

0.1 VA

± 1%

Frequency

0.01 Hz

± 0.01 Hz

45 … 65 Hz

Active Energy

1 W·h

± 1%

Reactive energy

1 VAr·h

± 1%

Voltage THD

% x 10

± 0.5%

10% … 120% of Un

Current THD

% x 10

± 0.5%

20% … 120% of In

PST Flicker

% x 10

± 5%

Voltage Imbalance

% x 10

Voltage Asymmetry

% x 10

Crest Factor

x100

± 0.5%

1.0…1.875

* The unit's accuracy in current and in power does not include the margins of error of the
clamps connected to it.

4.8

ENVIRONMENTAL CONDITIONS

Operating temperature


-10…+50 ºC

Storage temperature

-10…+60 ºC

Altitude

2,000 m

Humidity without condensation

5...95%



Advertising