22 FREQUENTLY ASKED QUESTIONS

22.1 CAN I EXPAND THE ANALYZER'S INTERNAL MEMORY?

Users can expand the unit's memory capacity by changing the SD. The SD must have FAT32
format and may have up to 32 Gb of capacity.

22.2 THE UNIT IS NOT RESPONDING TO THE BUTTONS. WHAT COULD BE

HAPPENING AND HOW CAN I FIX IT?

Generally the locking is caused by clicking a sequence of buttons that lock it out. To unlock the
buttons, briefly press the unit's off button. The unit will then respond to all buttons.

22.3 WHAT DOES THE UNIT LOG WHEN IT TAKES A SNAPSHOT?

The analyzer logs 1 wave shape cycle of the 9 channels with resolution of 128 samples per
channel, as well as the RMS values of the instantaneous, variables, harmonics, phasors and
energy. Maximum and minimum values, quality parameters and maximum demand.

22.4 WHAT DOES IT LOG WHEN IT CAPTURES THE WAVE SHAPE OF AN EVENT?

It logs 2 wave shape cycles, ½ of the previous cycle and 1½ cycles after the detection of the
event, with a resolution of 128 samples per channel.

22.5 WHAT SOFTWARE IS USED TO ANALYSE THE LOGGED DATA?

The data is downloaded and analysed with the Power Vision Plus software that comes with the
unit.