4 log.eva files – CIRCUTOR AR6 Series User Manual

Page 65

Advertising
background image

AR6 portable network analyzer

User Manual

Page 65 of 69

19.4 LOG.EVA FILES

The AR6 analyzer has a log type called EVA in which the device's events are stored. A
device event is understood as any change of the measurement configuration that
affects the header of STD files, such as switching the unit ON or OFF, modifying the
transformer’s ratios, battery charge status, deleting maximum values or other
parameters. The complete list of events is shown in Table 19-1.

Table 19-1.- Table of variables for LOG.EVA files

Event Name

Description

BAT_OFF

Battery level that causes the unit to switch off.

CLEAR_ENERGY

Deleting energy.

CLEAR_MAX_MIN

Deleting maximum values, minimum values or maximum and
minimum values.

CLEAR_MAX_DEMAND

Deleting maximum demand.

SETUP_CHANGED

Change of a configuration parameter other than transformer’s
ratios

SETUP_TRANS_RATIO

_CHANGED

Change of transformer’s ratio configurations

SETUP_TIME_CHANGED

Change of date and/or time

TRIGGER_ON

Entering in a trip time window (associated with the immediate
subsequent generation

of the REC_START event)

TRIGGER_OFF

Exiting a trip time window (associated with the immediate
subsequent generation

of the REC_STOP event)

DELETED_STD_FILE

Deleting configuration files due to erasing a measurement

POWER_ON

Unit switched on

POWER_OFF

Unit switched off

REC_STOP

Stop manual or trip logging

REC_START

Start manual or trip logging

TRIGGER_CONDITION_ON

Trip activation due to a variable condition

TRIGGER_CONDITION_OFF

Trip deactivation due to a variable condition

EVQ_STOP

Automatic deactivation of events or transients (after detecting 1
EVQ / TRN per second for 15 sec.)

EVQ_START

Automatic enabling of events or transients (after 10 min. has
elapsed since deactivation)

Advertising