10.2.5 Transients

The detection of transients lets the user detect different types of voltage wave defects. When
the user clicks on the transients menu option the screen in Fig. 10-11 or similar will appear.

Clicking the” Detection mode" window allows the selection among the following options:

Configurable options for detection method:

Peak

Wave

RMS Value

Disabled

Fig. 10-9.- Configurable options for capturing transients

PEAK

The detection of transients based on the peak value occurs when the absolute value of one or
several voltage samples exceed a certain threshold value set in this screen. The setting should
be large enough to avoid it from being tripped with normal amplitudes or even those slightly
above 110% of the nominal peak value.

The detection is based on phase-neutral voltage value. If there is no neutral, the set value
should be the maximum phase-phase voltage value divided by

√3

Fig. 10-10.- Peak value defect

Configurable Parameters:

Peak voltage in V phase to
neutral

Fig. 10-11.- Configuration for transient detection based on Peak value

WAVE

The detection of transients using the “wave” option occurs when there is a defect in the wave
shape so that the it exceeds the limits of a square defined by a threshold value (V phase to
neutral) and a duration (indicated in % of the period)