MAIN FEATURES

• Single or dual power supply configurations allow a wide range of output voltages:

Single power supply configuration:

≥12 V DC, ≤36.0 V DC input, powering both controller and TE device.

Dual power supply configuration:

≥12 V DC, ≤36.0 V DC at 150 mA minimum for controller circuitry

≥0 V DC, ≤36.0 V DC for TE device.

• Pulse-width modulated output: square wave, approximately 337 Hz, with soft start.

• Maximum output current: up to 20 A to thermoelectric device and up to 2.0 A per alarm circuit, 20 A maximum

combined output current (Note: controller does not have internal fuse protection).

• Analog signal-level output: provides true linear power control capability when used with a programmable linear

power supply.

• Bipolar (heat and cool) PID control.

• Best-case control stability ±0.01 °C (when controlling a cold plate).

• Proportional (P) bandwidth adjustment: 0.5 °C to 100.0 °C.

• Integral gain (I) adjustment: 0.00 to 10.00 repeats per minute.

• Derivative gain (D) adjustment: 0.00 to 10.00 cycles per minute.

• Built in Ramp / Soak with user programmable steps in PID mode, with separate PID parameters allowed for each

program step.

• Energy-saving Proportional + Deadband control mode allows the user to program a dead band where no cooling or

heating is required, then gradually applies cooling or heating power only as necessary.

• User programmable temperature sensor curve—allows for the use of a variety of thermistors or IC type sensors

(LM335, for example).

• Separately selectable temperature sensor types.

• Temperature control ranges:

1. -20 °C to +100 °C using the MP-3193 thermistor supplied with the controller.

2. Additional control ranges for optional thermistors are:

a. -40 °C to +70 °C using a 5k-1 TS-141 curve.

b. -20 °C to +85 °C using the 10k-1 TS-91 curve.

c. -15 °C to +80 °C using the 10k-2 TP-53 curve.

d. 0 °C to +150 °C using the 50k-1 TS-104 curve.

e. +25 °C to +199 °C using the 230k-1 TS-165 curve.

• (When using one of these control ranges, the thermistor you choose must have the same

response that matches the corresponding resistance-versus-temperature curve shown in the

appendix of the manual. A thermistor following the 10k-2 TP-53 curve, for example, is not a standard

product offered by TE Technology and must be purchased separately from a third party. Other

thermistors are available from www.tetech.com.)

3. Used defined sensor table can be used to provide a custom control range for use with different sensor

types.

• Optional secondary sensor input for sensing an alarm condition.

• Two available alarm outputs, capable of sinking up to 2 A each, for triggering alarms based on the primary (control)

sensor and/or secondary sensor.

• Enable/disable interlock: can be used with thermostats to shut off output power.

• Fan speed control: Alarm 1 output can be configured as a programmable PWM fan control for two-wire or three-

wire fans that are specifically designed for speed control.

• Operating temperature range (non-condensing, vertical orientation):

Minimum: 0 °C

Maximum: 45 °C

• Back-lit Liquid Crystal Display (LCD).

• USB (Universal Serial Bus) Interface.