7. PROPORTIONAL BANDWIDTH

Write Command: 1d

Read Command: 51

Interpret:

proportional bandwidth in °C.

For writing, multiply the desired bandwidth by 100

10

then convert to hexadecimal. For reading,

convert the returned hexadecimal to decimal, and then divide by 100

10

.

1.00

10

°C bandwidth would be 100

10

.

20.00

10

°C bandwidth would be 2000

10

.

8. INTEGRAL GAIN

Write Command: 1e

Read Command: 52

Interpret:

integral gain in Repeats/minute

For writing, multiply the desired integral gain by 100

10

then convert to hexadecimal. For reading,

convert to decimal then divide by 100

10

.

0.01 rep/min would be 1

10

.

1.00 rep/min would be 100

10

.

9. DERIVATIVE GAIN

Write Command: 1f

Read Command: 53

Interpret:

derivative gain in minutes.

For writing, multiply desired integral gain by 100

10

then convert to hexadecimal. For reading,

convert to decimal then divide by 100

10

.

0.01 min would be 1

10

.

1.00 min would be 100

10

.

10. ALARM1 TYPE

Write Command: 27

Read Command: 5b

Interpret:

0, no load effect; the controller will continue to provide output power

1, load off on alarm; the controller will turn off output power

11. ALARM2 TYPE

Write Command: 2a

Read Command: 5e

Interpret:

0 no load effect; the controller will continue to provide output power

1, load off on alarm; the controller will turn off output power

12. SENSOR1 CHOICE

Write Command: 20

Read Command: 54

Interpret:

0 == 5 kΩ thermistor

1 == 10 kΩ thermistor, type 1 (TS-91)

2 == 10 kΩ thermistor, type 2 (TP-53)

3 == 15 kΩ thermistor

4 == 50 kΩ thermistor

5 == 230 kΩ thermistor

6 == user defined table