10 alarm 2 function, Values: keep output on or turn output off, Default value = turn output off – TE Technology TC-720 User Manual

Page 36: 11 alarm latches, Default value = no latches, Descriptions

Advertising
background image

Note: If the controller senses an open circuit or a short circuit with respect to the thermistor, the controller will

signal an alarm condition (presuming it is not set to OFF). In addition, if the controller senses an open thermistor

circuit, T2 will not be displayed in the primary screen.

Using the GUI the user can configure ALARM 2 to operate from either the input 1 (control) sensor or the input 2

sensor. This selection is not available from the keypad. The factory default is for ALARM 2 to operate from the

input 2 sensor.

2.4.10 ALARM 2 FUNCTION

Values: KEEP OUTPUT ON or TURN OUTPUT OFF

Default value = TURN OUTPUT OFF

Description: This setting determines what action will be taken when there is an alarm condition on the secondary

sensor. When KEEP OUTPUT ON is selected, output power to the TE device stays on during the alarm condition,

and the alarm 2 signal on JP2-10 is activated. When TURN OFF OUTPUT is selected, output power to the TE device

is turned off, and the alarm 2 signal on JP2-10 is activated.

The ALARM 1 and ALARM 2 outputs on JP2-8 AND JP2-10 will momentarily pulse on and off several times

in the first second after the controller is turned on. This happens as the microprocessor in the controller

configures itself, regardless of any alarm condition.

2.4.11 ALARM LATCHES

Values: NO LATCHES, ALARMS 1&2 LATCH, ALARM2 LATCH, ALARM1 LATCH

Default value = NO LATCHES

Descriptions:

NO LATCHES: If an alarm condition occurs but then clears itself, the alarm signal will automatically turn off and

power to the TE device will be restored (assuming ALARM 1 FUNCTION and ALARM 2 FUNCTION are set to TURN

OUTPUT OFF).

If the alarm condition is recurring and the ALARM 1 FUNCTION and/or ALARM 2 FUNCTION is set to TURN

OUTPUT OFF, the TE device can be damaged by thermal fatigue stress imposed by repeated long-term

power cycling.

NOTE: The default deadband for the latch reset is 0 °C. However, the deadband can be reprogrammed using the

computer interface to allow for the latch to reset at a specified temperature difference above/below the alarm set

point. You can use the software provided with the controller or you can create your own software and use the

controller commands as described in “Serial Communications” in the appendix.

ALARMS 1&2 LATCH: if an alarm condition occurs from either the control or secondary sensor or both, the

controller will continue to signal an alarm until reset, even if the alarm condition is cleared. Power to the controller

must be turned off and then on again to turn off the alarm signal. Alternatively, press and hold the UP ARROW

button for three seconds to clear the alarm signal and reset the latches.

ALARM2 LATCH: if an alarm condition occurs from the secondary sensor, the controller will continue to signal the

alarm until reset, even if the alarm condition is cleared. Power to the controller must be turned off and then on

again to turn off the alarm. Alternatively, press and hold the UP ARROW button for three seconds to clear the

alarm and reset the latch.

ALARM1 LATCH: if an alarm condition occurs from the control sensor, the controller will continue to signal the

alarm until reset, even if the alarm condition is cleared. Power to the controller must be turned off and then on

again to turn off the alarm. Alternatively, press and hold the UP ARROW button for three seconds to clear the

alarm and reset the latch.

36

Advertising
This manual is related to the following products: